ELECTROCHEMICAL CORROSION TESTS FOR TANK 241-AY-101 CORE 325 SEGMENTS 16R1 & 16R2
The interstitial liquid in the double-shell tank 241-AY-101 settled solids layer is below the hydroxide chemistry control limit required by HNF-SD-WM-TSR-006, Tank Farms Technical Safety Requirements, Administrative Control 5.16, 'Corrosion Mitigation Controls'. Operating tanks outside of the specification may increase the propensity corrosion of the carbon steel wall. This report is concerned with generalized electrochemical corrosion mechanism that may occur at specific loci. All cyclic potentiodynamic polarization scans exhibited a negative hysteresis, scan reversing at lower current density, indicating that there was no pitting propensity. The general electrochemical corrosion rates ranged from 4.4E-02 to 1.5E-03 mpy with the first round of coupons, while the second round yielded corrosion rates of 2.5E-03 to 2.9E-02 mpy
Recommended from our members
CORROSION STUDY FOR THE EFFLUENT TREATMENT FACILITY CHROME (VI) REDUCTANT SOLUTION USING 304 AND 316L STAINLESS STEEL
This report documents the laboratory testing and analyses as directed under the test plan, RPP PLAN-34065, and documented in laboratory notebooks HNF 2742 and HNF-N-473-1. The purpose of this study was to evaluate and compare the electrochemical corrosion and pitting susceptibility of the 304 and 316L stainless steel in the acidified reducing solution that will be contained in either the secondary waste receiving tank or concentrate tank
Recommended from our members
ELECTROCHEMICAL CORROSION TESTING OF TANKS 241-AN-102 & 241-AP-107 & 241-AP-108 IN SUPPORT OF ULTRASONIC TESTING
This report presents the results of the corrosion rates that were measured using electrochemical methods for tanks 241-AN-102 (AN-102), 241-AP-107 (AP 107), and 241-AP-108 (AP-108) performed under test plant RPP-PLAN-38215. The steel used as materials of construction for AN and AP tank farms was A537 Class 1. Test coupons of A537 Class 1 carbon steel were used for corrosion testing in the AN-107, AP-107, and AP-108 tank waste. Supernate will be tested from AN-102, AP-107, and Ap-108. Saltcake testing was performed on AP-108 only
Outcome measures in post-stroke arm rehabilitation trials: do existing measures capture outcomes that are important to stroke survivors, carers, and clinicians?
Objective:
We sought to (1) identify the outcome measures currently used across stroke arm rehabilitation randomized trials, (2) identify and compare outcomes important to stroke survivors, carers and clinicians and (3) describe where existing research outcome measures capture outcomes that matter the most to stroke survivors, carers and clinicians and where there may be discrepancies.
Methods:
First, we systematically identified and extracted data on outcome measures used in trials within a Cochrane overview of arm rehabilitation interventions. Second, we conducted 16 focus groups with stroke survivors, carers and clinicians using nominal group technique, supplemented with eight semi-structured interviews, to identify these stakeholders’ most important outcomes following post-stroke arm impairment. Finally, we described the constructs of each outcome measure and indicated where stakeholders’ important outcomes were captured by each measure.
Results:
We extracted 144 outcome measures from 243 post-stroke arm rehabilitation trials. The Fugl-Meyer Assessment Upper Extremity section (used in 79/243 trials; 33%), Action Research Arm Test (56/243; 23%), and modified Ashworth Scale (53/243; 22%) were most frequently used. Stroke survivors (n = 43), carers (n = 10) and clinicians (n = 58) identified 66 unique, important outcomes related to arm impairment following stroke. Between one and three outcomes considered important by the stakeholders were captured by the three most commonly used assessments in research.
Conclusion:
Post-stroke arm rehabilitation research would benefit from a reduction in the number of outcome measures currently used, and better alignment between what is measured and what is important to stroke survivors, carers and clinicians
Recommended from our members
RESULTS OF THE EXAMINATION OF ELECTROCHEMICAL NOISE PROBE SPECIMENS REMOVED FROM TANK 241-AN-107 JUNE 2010
An Integrated Multi-function Corrosion Probe (IMCP) was installed in Tank 241-AN-107 on September 20, 2006. A portion of the probe was retrieved on June 8, 2010 and the sections holding the detectors were delivered to the 222-S Laboratory for analysis. The examination and disassembly of the probe sections encountered a number of challenges. However, disassembly and relevant analyses were successfully completed. The following summarizes our observations. Brittle failure of the fiberglass probe in the middle of detector 2 resulted in the recovery of only three vapor space C-rings and six supernatant bullet specimens. The design of the bullets and how they were attached to the probe made the recovery of the components more difficult. The use of glue/epoxy on the bullets and the attachment of the flat bottom of the bullets to the curved surface of the fiberglass probe body meant that weight loss on cleaning and surface area of the specimens could not be determined with acceptable accuracy. Macrophotography of all specimens reveals that corrosion was slight in the vapor space and extremely slight in the supernatant. The one pre-cracked C-ring recovered from the vapor space still had the stress bulge visible on the polished surface, indicating that crack propagation had not occurred in the tank. No photographs were taken of the C-ring before deployment. No further analysis was conducted on this specimen. A detailed discussion and photographic documentation are provided in this report
Recommended from our members
REPORT ON THE EFFECT OF TEMPERATURE AND AMMONIA CONCENTRATION ON A515 CARBON STEEL IN TANK 241 AY 101 SIMULANT
This report documents the results from RPP-PLAN-38676, Effect of Temperature and Ammonia Concentration on A515 Carbon Steel in Tank 241-AY-101 Simulant. The purpose of this test plan was to investigate the simulant formulated for the double-shell tank (DST) 241 AY 101 (AY 101) with the addition of ammonia. The simulant was formulated from the AY-101 condensate surface layer recipe used by CC Technologies{reg_sign} in the investigation of Hanford DST chemistry, under the Expert Panel on Corrosion. AY-101 is constructed from A515 grade 60 steel. The laboratory investigation used a cylindrical corrosion coupon from this steel formulation with a surface area of 5.64 square centimeters
RESULTS OF THE EXAMINATION OF ELECTROCHEMICAL NOISE PROBE SPECIMENS REMOVED FROM TANK 241-AN-107 JUNE 2010
An Integrated Multi-function Corrosion Probe (IMCP) was installed in Tank 241-AN-107 on September 20, 2006. A portion of the probe was retrieved on June 8, 2010 and the sections holding the detectors were delivered to the 222-S Laboratory for analysis. The examination and disassembly of the probe sections encountered a number of challenges. However, disassembly and relevant analyses were successfully completed. The following summarizes our observations. Brittle failure of the fiberglass probe in the middle of detector 2 resulted in the recovery of only three vapor space C-rings and six supernatant bullet specimens. The design of the bullets and how they were attached to the probe made the recovery of the components more difficult. The use of glue/epoxy on the bullets and the attachment of the flat bottom of the bullets to the curved surface of the fiberglass probe body meant that weight loss on cleaning and surface area of the specimens could not be determined with acceptable accuracy. Macrophotography of all specimens reveals that corrosion was slight in the vapor space and extremely slight in the supernatant. The one pre-cracked C-ring recovered from the vapor space still had the stress bulge visible on the polished surface, indicating that crack propagation had not occurred in the tank. No photographs were taken of the C-ring before deployment. No further analysis was conducted on this specimen. A detailed discussion and photographic documentation are provided in this report
Marked long-term decline in ambient CO mixing ratio in SE England, 1997–2014:Evidence of policy success in improving air quality
Atmospheric CO at Egham in SE England has shown a marked and progressive decline since 1997, following adoption of strict controls on emissions. The Egham site is uniquely positioned to allow both assessment and comparison of ‘clean Atlantic background’ air and CO-enriched air downwind from the London conurbation. The decline is strongest (approximately 50ppb per year) in the 1997–2003 period but continues post 2003. A ‘local CO increment’ can be identified as the residual after subtraction of contemporary background Atlantic CO mixing ratios from measured values at Egham. This increment, which is primarily from regional sources (during anticyclonic or northerly winds) or from the European continent (with easterly air mass origins), has significant seasonality, but overall has declined steadily since 1997. On many days of the year CO measured at Egham is now not far above Atlantic background levels measured at Mace Head (Ireland). The results are consistent with MOPITT satellite observations and ‘bottom-up’ inventory results. Comparison with urban and regional background CO mixing ratios in Hong Kong demonstrates the importance of regional, as opposed to local reduction of CO emission. The Egham record implies that controls on emissions subsequent to legislation have been extremely successful in the UK
On the Maxwell-Stefan approach to multicomponent diffusion
We consider the system of Maxwell-Stefan equations which describe
multicomponent diffusive fluxes in non-dilute solutions or gas mixtures. We
apply the Perron-Frobenius theorem to the irreducible and quasi-positive matrix
which governs the flux-force relations and are able to show normal ellipticity
of the associated multicomponent diffusion operator. This provides
local-in-time wellposedness of the Maxwell-Stefan multicomponent diffusion
system in the isobaric, isothermal case.Comment: Based on a talk given at the Conference on Nonlinear Parabolic
Problems in Bedlewo, Mai 200
Frequent use of paracetamol and risk of allergic disease among women in an Ethiopian population
Introduction
The hypothesis that paracetamol might increase the risk of asthma and other allergic diseases have gained support from a range of independent studies. However, in studies based in developed countries, the possibility that paracetamol and asthma are associated through aspirin avoidance is difficult to exclude.
Objectives
To explore this hypothesis among women in a developing country, where we have previously reported aspirin avoidance to be rare.
Methods
In 2005/6 a population based cohort of 1065 pregnant women was established in Butajira, Ethiopia and baseline demographic data collected. At 3 years post birth, an interview-based questionnaire administered to 945 (94%) of these women collected data on asthma, eczema, and hay fever in the past 12 month, frequency of paracetamol use and potential confounders. Allergen skin tests to Dermatophagoides pteronyssinus and cockroach were also performed. The independent effects of paracetamol use on allergic outcomes were determined using multiple logistic regression analysis.
Findings
The prevalence of asthma, eczema and hay fever was 1.7%, 0.9% and 3.8% respectively; of any one of these conditions 5.5%, and of allergen sensitization 7.8%. Paracetamol use in the past month was reported by 29%, and associations of borderline significance were seen for eczema (adjusted OR (95% CI) = 8.51 (1.68 to 43.19) for 1–3 tablets and 2.19 (0.36 to 13.38) for ≥4 tablets, compared to no tablets in the past month; overall p = 0.055) and for ‘any allergic condition’ (adjusted OR (95% CI) = 2.73 (1.22 to 6.11) for 1–3 tablets and 1.35 (0.67 to 2.70) for ≥4 tablets compared to 0 in the past month; overall p = 0.071).
Conclusions
This study provides further cross-sectional evidence that paracetamol use increases the risk of allergic disease
- …