    Analysis of a Costly Fiberglass-Polyester Air Filter Fire

    Get PDF
    In September 2020, a fire at a liquefied natural gas (LNG) plant in the Arctic areas of Norway received national attention. In an unengaged air intake, the heat exchanger designed to prevent ice damage during production mode, was supplied hot oil at 260 °C. In sunny weather, calm conditions, and 14 °C ambient temperature, overheating of the unengaged air intake filters (85% glass fiber and 15% polyester) was identified as a possible cause of ignition. Laboratory heating tests showed that the filter materials could, due to the rigid glass fibers carrying the polymers, glow like smoldering materials. Thus, self-heating as observed for cellulose-based materials was a possible ignition mechanism. Small-scale testing (10 cm × 10 cm and 8 cm stacked height) revealed that used filters with collected biomass, i.e., mainly pterygota, tended to self-heat at 20 °C lower temperatures than virgin filters. Used filter cassettes (60 cm by 60 cm and 50 cm bag depth) caused significant self-heating at 150 °C. At 160 °C, the self-heating took several hours before increased smoke production and sudden transition to flaming combustion. Since the engaged heat exchanger on a calm sunny day of ambient temperature 14 °C would result in temperatures in excess of 160 °C in an unengaged air intake, self-heating and transition to flaming combustion was identified as the most likely cause of the fire. Flames from the burning polymer filters resulted in heat exchanger collapse and subsequent hot oil release, significantly increasing the intensity and duration of the fire. Due to firewater damages, the plant was out of operation for more than 1.5 years. Better sharing of lessons learned may help prevent similar incidents in the future.publishedVersio

    Modelling breakdown of industrial thermal insulation during fire exposure

    Get PDF
    The aging of many of the installations in the oil and gas industry may increase the likelihood of loss of containment of flammable substances, which could lead to major accidents. Flame temperatures in a typical hydrocarbon fire may reach 1100–1200 °C, which are associated with heat flux levels between 250 and 350 kW/m2. To limit or delay the escalation of an initial fire, passive fire protection (PFP) can be an effective barrier. Additionally, both equipment and piping may require thermal insulation for heat or cold conservation. Previous studies have investigated whether thermal insulation alone may protect the equipment for a required time period, e.g., until adequate depressurization is achieved. The present study entails the development of a numerical model for predicting the heat transport through a multi-layer wall of a distillation column exposed to fire. The outer surface is covered by stainless-steel weather protective cladding, followed by PFP, thermal insulation, and finally an inner column of carbon steel of variable thicknesses. The model for the breakdown of thermal insulation is based on observed dimensional changes and independent measurements of the thermal conductivity of the insulation after heat treatment. The calculated temperature profiles of thermally insulated carbon steel during fire exposure are compared to fire test results for carbon steel with thicknesses of 16, 12, 6 and 3 mm. The model's predictions agree reasonably well with the experiments. The degradation of the thermal insulation at temperatures above 1100 °C limits its applicability as fire protection, especially for low carbon-steel thickness. However, the model predicts that adding a 10-mm layer of more heat-resistant insulation (PFP) inside the fire-exposed cladding may considerably extend the time to breakdown of the thermal insulation.publishedVersio

    Cloud-based Implementation and Validation of a Predictive Fire Risk Indication Model

    Get PDF
    The high representation of wooden houses in Norwegian cities combined with periods of dry and cold climate during the winter time often results in a high risk of severe fires. This makes it important for public authorities and fire departments to have an accurate estimate of the current fire risk in order to take proper precautions. We report on the implementation of a predictive mathematical model based on first order principles which exploits cloud-provided measurements from weather stations and weather forecasts from the Norwegian Meteorological Institute to predict the current and future fire risk at a given geographical location. We have experimentally validated the model during the winter 2018-2019 at selected geographical locations, and by considering weather data from the time of several historical fires. Our results show that our cloud and web-based implementation is both time and storage efficient, and capable of being able to accurately predict the fire risk measured in terms of the estimated time to ashover. The paper demonstrates that our methodology in the near future may become a valuable risk predicting tool for Norwegian fire brigades

    Industrial Thermal Insulation Properties above Sintering Temperatures

    Get PDF
    Processing highly flammable products, the oil and gas (O&G) industry can experience major explosions and fires, which may expose pressurized equipment to high thermal loads. In 2020, oil fires occurred at two Norwegian O&G processing plants. To reduce the escalation risk, passive fire protectionmay serve as a consequence-reducing barrier. For heat or cold conservation, equipment and piping often require thermal insulation, which may offer some fire protection. In the present study, a representative thermal insulation (certified up to 700 °C) was examined with respect to dimensional changes and thermal transport properties after heat treatment to temperatures in the range of 700 °C to 1200 °C. Post heat treatment, the thermal conductivity of each test specimen was recorded at ambient temperature and up to 700 _C, which was the upper limit for the applied measurement method. Based on thermal transport theory for porous and/or amorphous materials, the thermal conductivity at the heat treatment temperature above 700 °C was estimated by extrapolation. The dimensional changes due to, e.g., sintering, were also analyzed. Empirical equations describing the thermal conductivity, the dimensional changes and possible crack formation were developed. It should be noted that the thermal insulation degradation, especially at temperatures approaching 1200 °C, is massive. Thus, future numerical modeling may be difficult above 1150 °C, due to abrupt changes in properties as well as crack development and crack tortuosity. However, if the thermal insulation is protected by a thin layer of more robust material, e.g., passive fire protection to keep the thermal insulation at temperatures below 1100 °C, future modeling seems promising.publishedVersio

    Reducing Wooden Structure and Wildland-Urban Interface Fire Disaster Risk through Dynamic Risk Assessment and Management

    Get PDF
    In recent years, severe and deadly wildland-urban interface (WUI) fires have resulted in an increased focus on this particular risk to humans and property, especially in Canada, USA, Australia, and countries in the Mediterranean area. Also, in areas not previously accustomed to wildfires, such as boreal areas in Sweden, Norway, and in the Arctic, WUI fires have recently resulted in increasing concern. January 2014, the most severe wooden town fire in Norway since 1923 raged through Lærdalsøyri. Ten days later, a wildfire raged through the scattered populated community of Flatanger and destroyed even more structures. These fires came as a surprise to the fire brigades and the public. We describe and analyze a proposed way forward for exploring if and how this increasing fire incidence can be linked to concomitant changes in climate, land-use, and habitat management; and then aim at developing new dynamic adaptive fire risk assessment and management tools. We use coastal Norway as an example and focus on temporal changes in fire risk in wooden structure settlements and in the Norwegian Calluna vulgaris L. dominated WUI. In this interface, the fire risk is now increasing due to a combination of land-use changes, resulting in large areas of early successional vegetation with an accumulation of biomass, and the interactive effects of climatic changes resulting in increased drought risk. We propose a novel bow-tie framework to explore fire risk and preventive measures at various timescales (years, months, weeks, hours) as a conceptual model for exploring risk contributing factors and possibilities for risk management. Ignition is the top event of the bow-tie which has the potential development towards a fire disaster as a worst case outcome. The bow-tie framework includes factors such as changes in the built environment and natural habitat fuel moisture content due to the weather conditions, WUI fuel accumulation, possibly improved ecosystem management, contribution by civic prescribed burner groups, relevant fire risk modeling, and risk communication to the fire brigades and the public. We propose an interdisciplinary research agenda for developing this framework and improving the current risk understanding, risk communication, and risk management. This research agenda will represent important contributions in paving the road for fire disaster prevention in Norway, and may provide a model for other systems and regions.publishedVersio

    Modeling Skin Injury from Hot Rice Porridge Spills

    No full text
    The present work analyzes skin burns from spills of hot rice and milk products. The traditional Norwegian rice porridge serves as an example. By testing spills on objects emulating an arm, it was concluded that spills were seldom thinner than 3 mm, and stayed in place due to the viscosity of the porridge for more than one minute. The Pennes bioheat equation was solved numerically for such spills, including heat conduction to the skin and convective heat losses from the porridge surface. Temperatures were analyzed in the porridge and skin layers, and the resulting skin injury was calculated based on the basal layer temperature. Parameters influencing burn severity, such as porridge layer thickness, porridge temperature, removal of the porridge and thermal effects of post scald tempered (15 °C) water cooling were analyzed. The spilled porridge resulted in a prolonged heat supply to the skin, and the skin injury developed significantly with time. The porridge temperature turned out to be the most important injury parameter. A 70 °C porridge temperature could develop superficial partial-thickness burns. Porridge temperatures at processing temperatures nearly instantly developed severe burns. It was demonstrated that prompt removal of the hot porridge significantly reduced the injury development. The general advice is to avoid serving porridge and similar products at temperatures above 65 °C and, if spilled on the skin, to remove it quickly. After such scald incidents, it is advised to cool the injured area by tempered water for a prolonged period to stimulate healing

    Analysis of Expected Skin Burns from Accepted Process Flare Heat Radiation Levels to Public Passersby

    No full text
    Hot flaring, even from quite high flare stacks, may result in significant heat radiation outside a facility to, e.g., public roads where random passersby may be exposed. The present study suggests a novel method for analyzing a typical flare heat radiation exposure and investigates skin burns that may be inflicted on an exposed person if a facility needs to depressurize in an emergency situation. A typical radiation field from an ignited natural gas vent was taken as the boundary condition, and these values were compared to radiation levels mentioned by the American Petroleum Institute (API 521), e.g., 1.58 kW/m2 and above. Due to facility perimeter fences along roads in larger industry areas, it was assumed that an exposed person may flee along a road rather than in the ideal direction away from the flare. It was assumed that naked skin, e.g., a bare shoulder or a bald head is exposed. The Pennes bioheat equation was numerically solved for the skin layers while the person escapes along the road. Sun radiation and convective heat exchange to the ambient air were included, and the subsequent skin injury was calculated based on the temperature development in the basal layer. Parameters affecting burn severity, such as heat radiation, solar radiation, and convective heat transfer coefficient, were analyzed. For small flares and ignited small cold vents, no skin burn would be expected for 1.58 kW/m2 or 3.16 kW/m2 maximum heat radiation at the skin surface. However, higher flare rates corresponding to, e.g., 4.0 kW/m2 maximum flare heat radiation to the skin, resulted both in higher basal layer temperatures and longer exposure time, thus increasing the damage integral significantly. It is demonstrated that the novel approach works well. In future studies, it may, e.g., be extended to cover escape through partly shielded escape routes

    Modeling Skin Injury from Hot Rice Porridge Spills

    No full text
    The present work analyzes skin burns from spills of hot rice and milk products. The traditional Norwegian rice porridge serves as an example. By testing spills on objects emulating an arm, it was concluded that spills were seldom thinner than 3 mm, and stayed in place due to the viscosity of the porridge for more than one minute. The Pennes bioheat equation was solved numerically for such spills, including heat conduction to the skin and convective heat losses from the porridge surface. Temperatures were analyzed in the porridge and skin layers, and the resulting skin injury was calculated based on the basal layer temperature. Parameters influencing burn severity, such as porridge layer thickness, porridge temperature, removal of the porridge and thermal effects of post scald tempered (15 °C) water cooling were analyzed. The spilled porridge resulted in a prolonged heat supply to the skin, and the skin injury developed significantly with time. The porridge temperature turned out to be the most important injury parameter. A 70 °C porridge temperature could develop superficial partial-thickness burns. Porridge temperatures at processing temperatures nearly instantly developed severe burns. It was demonstrated that prompt removal of the hot porridge significantly reduced the injury development. The general advice is to avoid serving porridge and similar products at temperatures above 65 °C and, if spilled on the skin, to remove it quickly. After such scald incidents, it is advised to cool the injured area by tempered water for a prolonged period to stimulate healing

    Modeling Burns for Pre-Cooled Skin Flame Exposure

    No full text
    On a television show, a pre-cooled bare-skinned person (TV host) passed through engulfing kerosene flames. The assumption was that a water film should protect him during 0.74 s flame exposure in an environment of 86 kW/m2 heat flux. The TV host got light burn inflammation on the back, arms and legs. The present work studies skin temperatures and burn damage integral of such dangerous flame exposure. The skin temperature distribution during water spray pre-cooling, transport to the flames, flame exposure, transport to the water pool, and final water pool cooling is modelled numerically. Details of the temperature development of the skin layers are presented, as well as the associated damage integral. It is shown that 5 °C water spray applied for a 30 s period pre-cooled the skin sufficiently to prevent severe skin injury. Soot marks indicate that the water layer evaporated completely in some areas resulting in skin flame contact. This exposed dry skin directly to the flames contributing significantly to the damage integral. It is further analyzed how higher water temperature, shorter pre-cooling period or longer flame exposure influence the damage integral. It is evident that minor changes in conditions could lead to severe burns and that high heat flux levels at the end of the exposure period are especially dangerous. This flame stunt should never be repeated

    Skin temperatures of a pre-cooled wet person exposed to engulfing flames

    No full text
    In a television show, a wetted bare-skinned person slid through engulfing kerosene pool fire flames. The 0.74 s flame exposure resulted in pain and light sun burns. The heat and mass transfer involved in this dangerous stunt have been analyzed in order to evaluate whether or not the thin water layer represented an important heat protection measure. It is estimated that the wetted person was exposed to heat fluxes in the range of 80–90 kW/m2. Analytical solutions of the heat equation were used to evaluate water-spray pre-cooling, heating during flame exposure and post-flame relaxation of skin temperature gradients. It is shown that the water layer carried on the skin into the flames represented limited heat protection. The 30 s cold water-spray pre-cooling prior to the flame exposure was the most important heat protection mechanism. Larger flames of higher emissivity, longer period of flame exposure, warmer pre-cooling water or shorter pre-cooling period would most likely have resulted in severe skin burns
    • …