3,646 research outputs found
PMU-Based ROCOF Measurements: Uncertainty Limits and Metrological Significance in Power System Applications
In modern power systems, the Rate-of-Change-of-Frequency (ROCOF) may be
largely employed in Wide Area Monitoring, Protection and Control (WAMPAC)
applications. However, a standard approach towards ROCOF measurements is still
missing. In this paper, we investigate the feasibility of Phasor Measurement
Units (PMUs) deployment in ROCOF-based applications, with a specific focus on
Under-Frequency Load-Shedding (UFLS). For this analysis, we select three
state-of-the-art window-based synchrophasor estimation algorithms and compare
different signal models, ROCOF estimation techniques and window lengths in
datasets inspired by real-world acquisitions. In this sense, we are able to
carry out a sensitivity analysis of the behavior of a PMU-based UFLS control
scheme. Based on the proposed results, PMUs prove to be accurate ROCOF meters,
as long as the harmonic and inter-harmonic distortion within the measurement
pass-bandwidth is scarce. In the presence of transient events, the
synchrophasor model looses its appropriateness as the signal energy spreads
over the entire spectrum and cannot be approximated as a sequence of
narrow-band components. Finally, we validate the actual feasibility of
PMU-based UFLS in a real-time simulated scenario where we compare two different
ROCOF estimation techniques with a frequency-based control scheme and we show
their impact on the successful grid restoration.Comment: Manuscript IM-18-20133R. Accepted for publication on IEEE
Transactions on Instrumentation and Measurement (acceptance date: 9 March
2019
Smart Power Grid Synchronization With Fault Tolerant Nonlinear Estimation
Effective real-time state estimation is essential for smart grid synchronization, as electricity demand continues to grow, and renewable energy resources increase their penetration into the grid. In order to provide a more reliable state estimation technique to address the problem of bad data in the PMU-based power synchronization, this paper presents a novel nonlinear estimation framework to dynamically track frequency, voltage magnitudes and phase angles. Instead of directly analyzing in abc coordinate frame, symmetrical component transformation is employed to separate the positive, negative, and zero sequence networks. Then, Clarke\u27s transformation is used to transform the sequence networks into the αβ stationary coordinate frame, which leads to system model formulation. A novel fault tolerant extended Kalman filter based real-time estimation framework is proposed for smart grid synchronization with noisy bad data measurements. Computer simulation studies have demonstrated that the proposed fault tolerant extended Kalman filter (FTEKF) provides more accurate voltage synchronization results than the extended Kalman filter (EKF). The proposed approach has been implemented with dSPACE DS1103 and National Instruments CompactRIO hardware platforms. Computer simulation and hardware instrumentation results have shown the potential applications of FTEKF in smart grid synchronization
Comparing Kalman Filters and Observers for Power System Dynamic State Estimation with Model Uncertainty and Malicious Cyber Attacks
Kalman filters and observers are two main classes of dynamic state estimation
(DSE) routines. Power system DSE has been implemented by various Kalman
filters, such as the extended Kalman filter (EKF) and the unscented Kalman
filter (UKF). In this paper, we discuss two challenges for an effective power
system DSE: (a) model uncertainty and (b) potential cyber attacks. To address
this, the cubature Kalman filter (CKF) and a nonlinear observer are introduced
and implemented. Various Kalman filters and the observer are then tested on the
16-machine, 68-bus system given realistic scenarios under model uncertainty and
different types of cyber attacks against synchrophasor measurements. It is
shown that CKF and the observer are more robust to model uncertainty and cyber
attacks than their counterparts. Based on the tests, a thorough qualitative
comparison is also performed for Kalman filter routines and observers.Comment: arXiv admin note: text overlap with arXiv:1508.0725
Analysis of the energy harvesting performance of a piezoelectric bender outside its resonance
When the frequency of the source of vibration of a piezolectric generator is significantly different from its eigenfrequency, the dielectric power losses become prominent and decrease the amount of power which is practically harvested. For off-resonance vibrating frequencies, the optimal operating conditions can be obtained with a Maximum Power Point Tracking method. This paper introduces complex phasors in the study of power conversion for piezoelectric generators. These complex phasors are used to describe three strategies which help simplify the tracking of the optimal generator output power for vibration frequencies which are away from resonance. Experimental results obtained on a prototype illustrate and confirm the approach with the phasor approaches illustrate and confirm the success of the proposed optimal power tracking strategies. Finally, we show that the efficiency results of each strategy depend on whether they are used inside or outside a frequency bandwidth around the eigenfrequency, and that the length of this bandwidth depends on the excitation amplitude.IRCICA Stimtac Project, INRIA Mint Project
- …