4 research outputs found

    Gated pipelined folding ADC based low power sensor for large-scale radiometric partial discharge monitoring

    Get PDF
    Partial discharge is a well-established metric for condition assessment of high-voltage plant equipment. Traditional techniques for partial discharge detection involve physical connection of sensors to the device under observation, limiting sensors to monitoring of individual apparatus, and therefore, limiting coverage. Wireless measurement provides an attractive low-cost alternative. The measurement of the radiometric signal propagated from a partial discharge source allows for multiple plant items to be observed by a single sensor, without any physical connection to the plant. Moreover, the implementation of a large-scale wireless sensor network for radiometric monitoring facilitates a simple approach to high voltage fault diagnostics. However, accurate measurement typically requires fast data conversion rates to ensure accurate measurement of faults. The use of high-speed conversion requires continuous high-power dissipation, degrading sensor efficiency and increasing cost and complexity. Thus, we propose a radiometric sensor which utilizes a gated, pipelined, sample-and-hold based folding analogue-todigital converter structure that only samples when a signal is received, reducing the power consumption and increasing the efficiency of the sensor. A proof of concept circuit has been developed using discrete components to evaluate the performance and power consumption of the system

    Improved time-frequency de-noising of acoustic signals for underwater detection system

    Get PDF
    The capability to communicate and perform target localization efficiently in underwater environment is important in many applications. Sound waves are more suitable for underwater communication and target localization because attenuation in water is high for electromagnetic waves. Sound waves are subjected to underwater acoustic noise (UWAN), which is either man-made or natural. Optimum signal detection in UWAN can be achieved with the knowledge of noise statistics. The assumption of Additive White Gaussian noise (AWGN) allows the use of linear correlation (LC) detector. However, the non-Gaussian nature of UWAN results in the poor performance of such detector. This research presents an empirical model of the characteristics of UWAN in shallow waters. Data was measured in Tanjung Balau, Johor, Malaysia on 5 November 2013 and the analysis results showed that the UWAN has a non-Gaussian distribution with characteristics similar to 1/f noise. A complete detection system based on the noise models consisting of a broadband hydrophone, time-frequency distribution, de-noising method, and detection is proposed. In this research, S-transform and wavelet transform were used to generate the time-frequency representation before soft thresholding with modified universal threshold estimation was applied. A Gaussian noise injection detector (GNID) was used to overcome the problem of non-Gaussianity of the UWAN, and its performance was compared with other nonlinear detectors, such as locally optimal (LO) detector, sign correlation (SC) detector, and more conventionally matched filter (MF) detector. This system was evaluated on two types of signals, namely fixed-frequency and linear frequency modulated signals. For de-noising purposes, the S-transform outperformed the wavelet transform in terms of signal-to-noise ratio and root-mean-square error at 4 dB and 3 dB, respectively. The performance of the detectors was evaluated based on the energy-to-noise ratio (ENR) to achieve detection probability of 90% and a false alarm probability of 0.01. Thus, the ENR of the GNID using S-transform denoising, LO detector, SC detector, and MF detector were 8.89 dB, 10.66 dB, 12.7dB, and 12.5 dB, respectively, for the time-varying signal. Among the four detectors, the proposed GNID achieved the best performance, whereas the LC detector showed the weakest performance in the presence of UWAN

    An Accurate and Efficient Time Delay Estimation Method of Ultra-High Frequency Signals for Partial Discharge Localization in Substations

    Get PDF
    Partial discharge (PD) localization in substations based on the ultra-high frequency (UHF) method can be used to efficiently assess insulation conditions. Localization accuracy is affected by the accuracy of the time delay (TD) estimation, which is critical for PD localization in substations. A review of existing TD estimation methods indicates that there is a need to develop methods that are both accurate and computationally efficient. In this paper, a novel TD estimation method is proposed to improve both accuracy and efficiency. The TD is calculated using an improved cross-correlation algorithm based on full-wavefronts of array UHF signals, which are extracted using the minimum cumulative energy method and zero-crossing points searching methods. The cross-correlation algorithm effectively suppresses the TD error caused by differences between full-wavefronts. To verify the method, a simulated PD source test in a laboratory and a field test in a 220 kV substation were carried out. The results show that the proposed method is accurate even in case of low signal-to-noise ratio, but with greatly improved computational efficiency

    An Ultrahigh Frequency Partial Discharge Signal De-Noising Method Based on a Generalized S-Transform and Module Time-Frequency Matrix

    No full text
    Due to electromagnetic interference in power substations, the partial discharge (PD) signals detected by ultrahigh frequency (UHF) antenna sensors often contain various background noises, which may hamper high voltage apparatus fault diagnosis and localization. This paper proposes a novel de-noising method based on the generalized S-transform and module time-frequency matrix to suppress noise in UHF PD signals. The sub-matrix maximum module value method is employed to calculate the frequencies and amplitudes of periodic narrowband noise, and suppress noise through the reverse phase cancellation technique. In addition, a singular value decomposition de-noising method is employed to suppress Gaussian white noise in UHF PD signals. Effective singular values are selected by employing the fuzzy c-means clustering method to recover the PD signals. De-noising results of simulated and field detected UHF PD signals prove the feasibility of the proposed method. Compared with four conventional de-noising methods, the results show that the proposed method can suppress background noise in the UHF PD signal effectively, with higher signal-to-noise ratio and less waveform distortion
    corecore