6 research outputs found

    Numerical simulation of the alba synchrotron light source cooling system response to pump start-up and shut-down

    Get PDF
    The ALBA Synchrotron Light Source cooling system is submitted to regular pump start-ups and shut-downs. Moreover, pumps can trip due to motor power failures. As a result, the piping system can be subjected to surges and pressure oscillations. The 1D thermo-fluid simulation software FlowmasterÂż has been used to predict these transient conditions taking into account the fluid compressibility, the pipe elasticity, the characteristic time response of the check valves and the pump/motors moments of inertia. During pump start-ups, significant pressure rises are detected that can be reduced by readjusting the PID controller parameters. Unexpected pump shutdowns do not appear to provoke significant water hammer conditions. However, pressure fluctuations are generated mainly in the same pumping line but also in the rest of the system due to the particular common return configuration. In all the cases the pressure regulation mechanisms acting on the pump rotating speeds serve to attenuate the consequences of these transients. Finally, the feasibility of the model to simulate the effect on the system response of trapped air inside the pipes has also been evaluated.Postprint (published version

    Numerical simulation of the alba synchrotron light source cooling system response for failure prevention

    Get PDF
    The ALBA Synchrotron Light Source cooling system is designed with a common return pipe that interconnects the four consumption rings. Such configuration is believed to compromise its optimal operation. To understand its thermo-fluid dynamic behaviour, a detailed 1D model has been built comprising all the components such as the pipes, fittings, bends, valves, pumping stations, heat exchangers and so on, and the various regulation mechanisms. Preliminarily, the model results in steady state operating conditions have been compared with experimental measurements and the maximum deviations have been found below 13%. Then, a series of transient numerical simulations have been carried out to determine the system response. Specifically, effects of the blockage and leakage of a consumption line as well as the increase and decrease of heat duty for the tunnel rings have been investigated. As a result, the stability of the system has been evaluated and the operational limits have been estimated in front of hydraulic and thermal load variations. Moreover, particular behaviours have been identified which can be used to design monitoring and control strategies to prevent unexpected failures.Postprint (published version

    Thermo-fluid numerical simulation of the crotch absorbers’ cooling pinholes for alba storage ring

    Get PDF
    The ALBA Synchrotron Light Facility crotch absorbers, that remove the unused storage ring radiation, incorporate an internal cooling system composed by a number of parallel pinholes and by the corresponding stainless steel inner tubes inserted into each of them. Water flows in the resulting annular sections to evacuate the total heat power. Around each inner tube, a spiral wire is fixed along the whole length with a given pitch height in order to enhance the convection heat transfer. The influence of several design parameters on the absorber thermo-fluid behaviour has been evaluated by means of the CFD software ANSYS CFXÂż. In particular, the wall heat transfer coefficients and the pressure losses through a single pinhole have been evaluated for a range of different flow rates and pitch heights. Moreover, some modifications of the end wall geometry have been simulated as well as the effect of reversing the flow direction inside the channels. Finally, the critical crotch absorber type 3 has also been simulated and the limiting pitch height-flow rate combinations have been found based on the available driving pressure of the cooling system.Postprint (published version

    Numerical simulation of the alba synchrotron light source cooling system response to pump start-up and shut-down

    No full text
    The ALBA Synchrotron Light Source cooling system is submitted to regular pump start-ups and shut-downs. Moreover, pumps can trip due to motor power failures. As a result, the piping system can be subjected to surges and pressure oscillations. The 1D thermo-fluid simulation software FlowmasterÂż has been used to predict these transient conditions taking into account the fluid compressibility, the pipe elasticity, the characteristic time response of the check valves and the pump/motors moments of inertia. During pump start-ups, significant pressure rises are detected that can be reduced by readjusting the PID controller parameters. Unexpected pump shutdowns do not appear to provoke significant water hammer conditions. However, pressure fluctuations are generated mainly in the same pumping line but also in the rest of the system due to the particular common return configuration. In all the cases the pressure regulation mechanisms acting on the pump rotating speeds serve to attenuate the consequences of these transients. Finally, the feasibility of the model to simulate the effect on the system response of trapped air inside the pipes has also been evaluated

    Thermo-fluid numerical simulation of the crotch absorbers’ cooling pinholes for alba storage ring

    No full text
    The ALBA Synchrotron Light Facility crotch absorbers, that remove the unused storage ring radiation, incorporate an internal cooling system composed by a number of parallel pinholes and by the corresponding stainless steel inner tubes inserted into each of them. Water flows in the resulting annular sections to evacuate the total heat power. Around each inner tube, a spiral wire is fixed along the whole length with a given pitch height in order to enhance the convection heat transfer. The influence of several design parameters on the absorber thermo-fluid behaviour has been evaluated by means of the CFD software ANSYS CFXÂż. In particular, the wall heat transfer coefficients and the pressure losses through a single pinhole have been evaluated for a range of different flow rates and pitch heights. Moreover, some modifications of the end wall geometry have been simulated as well as the effect of reversing the flow direction inside the channels. Finally, the critical crotch absorber type 3 has also been simulated and the limiting pitch height-flow rate combinations have been found based on the available driving pressure of the cooling system

    Numerical modelling of the cooling system at alba synchrotron radiation facility to understand its performance

    No full text
    The ALBA Synchrotron Light Source in Barcelona (Spain) requires a reliable, stable and adequate cooling system for its optimal operation. The current design with four long and intricate consumption lines with a ring type piping layout (270 m perimeter) and a common return pipe is believed to compromise the operability and to promote the trapping of air pockets. In order to improve its performance, a better understanding of the thermo-fluid dynamic behaviour is required that permits to opmitize the system and to anticipate unexpected failures. For that, a detailed 1D model has been built with Flowmaster® software comprising all the components and the various regulation mechanisms to control fluid temperature and pressure. Preliminarily, the model has been validated in steady state operating conditions against experimental measurements showing good agreement. Then, a series of specific steady and transient numerical simulations have been carried out to determine the system response. In particular, the effects of blockage and leakage as well as the increase or decrease of heat duty have been analysed. Furthermore, the best flow distribution through the rings has also been found to reduce the air content by maximizing the velocities.Postprint (published version