6 research outputs found
The use of computer models to predict temperature and smoke movement in high bay spaces
The Building and Fire Research Laboratory (BFRL) was given the opportunity to make measurements during fire calibration tests of the heat detection system in an aircraft hangar with a nominal 30.4 (100 ft) ceiling height near Dallas, TX. Fire gas temperatures resulting from an approximately 8250 kW isopropyl alcohol pool fire were measured above the fire and along the ceiling. The results of the experiments were then compared to predictions from the computer fire models DETACT-QS, FPETOOL, and LAVENT. In section A of the analysis conducted, DETACT-QS AND FPETOOL significantly underpredicted the gas temperature. LAVENT at the position below the ceiling corresponding to maximum temperature and velocity provided better agreement with the data. For large spaces, hot gas transport time and an improved fire plume dynamics model should be incorporated into the computer fire model activation routines. A computational fluid dynamics (CFD) model, HARWELL FLOW3D, was then used to model the hot gas movement in the space. Reasonable agreement was found between the temperatures predicted from the CFD calculations and the temperatures measured in the aircraft hangar. In section B, an existing NASA high bay space was modeled using the CFD model. The NASA space was a clean room, 27.4 m (90 ft) high with forced horizontal laminar flow. The purpose of this analysis is to determine how the existing fire detection devices would respond to various size fires in the space. The analysis was conducted for 32 MW, 400 kW, and 40 kW fires
Quantitative Evaluation of Fire and EMS Mobilization Times
Quantitative Evaluation of Fire and EMS Mobilization Times presents comprehensive empirical data on fire emergency and EMS call processing and turnout times, and aims to improve the operational benchmarks of NFPA peer consensus standards through a close examination of real-world data. The book also identifies and analyzes the elements that can influence EMS mobilization response times. Quantitative Evaluation of Fire and EMS Mobilization Times is intended for practitioners as a tool for analyzing fire emergency response times and developing methods for improving them. Researchers working in