Fleet Asset Management Opportunities Arising from Transient Monitoring of Power Transformers and Shunt Reactors
Power transformers and shunt reactors are strategic assets for every system operator and their downtime should be kept as low and controlled as
possible. During their multi-decade service life, they are regularly exposed to transient overvoltages. These situations stress their insulation systems
and can cause accelerated deterioration and aging. Since the shapes of these overvoltages are usually unknown, an additional approach to assessing
the health index can be realized using monitoring systems with transient recorders. Analyzing the transient overvoltages using frequency domain
severity factor, a quantification of additional stress on the transformer’s/shunt reactor’s insula