3 research outputs found

    Disturbance size estimation in Great Britain power system including combined cycle gas turbine power stations

    Get PDF
    With the substantial popularity of combined cycle gas turbine (CCGT) power plants in the nowadays power systems, special care must be taken to regulate frequency due to unique frequency response characteristic of the full-loaded CCGT units. This unique feature is documented in the literature; however, its effect on determining frequency response of the power systems was not addressed in detail. This study proposes a new analytical method to achieve a more accurate estimated size of a loss-of-generation disturbance. This method considers demand-side power deviations and transmission lines power loss as well as unique frequency response of the CCGT units following the event. Firstly, it is exposed that there is an approximately linear relationship between power and frequency deviations of these plants in a real-world power system despite the complexity of the CCGT model. This relationship may be represented by a negative droop gain. Next, the derived CCGT’s linear characteristic is formulated in the disturbance size estimation process. Finally, the effectiveness of the proposed modifications is demonstrated through extensive simulations on a 36-zone Great Britain equivalent test system.© 2023 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY license (http://creativecommons.org/licenses/by/4.0/).fi=vertaisarvioitu|en=peerReviewed

    Data-driven risk-averse stochastic self-scheduling for combined-cycle units

    No full text
    202304 bckwAccepted ManuscriptOthersU.S. National Science Foundation; Hong Kong Polytechnic UniversityPublishe

    Data-Driven Risk-Averse Stochastic Self-Scheduling for Combined-Cycle Units

    No full text
    corecore