A general methodology for energy comparison of intermediate configurations in two-stage vapour compression refrigeration systems

Abstract

The aim of the present paper is to describe a general methodology suitable for analysing any intermediate configuration considered in staged vapour compression refrigeration cycles. This general methodology only depends on two basic parameters related to the subcooling and desuperheating obtained in the inter-stage system. A COP expression based on the two basic parameters was obtained from the general configuration. By means of its particularization to seven common configurations, it was then possible to make an energy comparison of the various configurations working with two fluids appropriated for the low temperature domain such as ammonia and R-404A

Similar works

Full text

thumbnail-image

Repositori Institucional de la Universitat Jaume I

redirect
Last time updated on 17/11/2016

Having an issue?

Is data on this page outdated, violates copyrights or anything else? Report the problem now and we will take corresponding actions after reviewing your request.