IMPINGEMENT COOLING OF A SEMI-CIRCULAR CONCAVE CHANNEL BY 2D AIR-JET

Abstract

This study provides a numerical solution to the flow in a cylindrical cavity of which the upper wall contains a twodimensional slot. The air injected through the slot impinges and diffuses laterally on the lower wall. The jet enfluxed through the slot is assumed to have uniform velocity and temperature, and the temperature at the lower wall is kept constant. The resulting Navier-Stokes equations are solved by transforming simpler algorithm into a form useably in cylindrical co-ordinate system. The effect of cavity curvature, and the height ratio on velocity and pressure distribution is analyzed. The jet Reynolds number ranged from 100 to 1500 in the analysis

Similar works

Full text

thumbnail-image

Directory of Open Access Journals

redirect
Last time updated on 09/08/2016

This paper was published in Directory of Open Access Journals.

Having an issue?

Is data on this page outdated, violates copyrights or anything else? Report the problem now and we will take corresponding actions after reviewing your request.