Electrical and Electronic Engineering, Imperial College London
Doi
Abstract
Application of wide-area monitoring and control for future smart grids with substantial
wind penetration and advanced network control options through FACTS and HVDC
(both point-to-point and multi-terminal) is the subject matter of this thesis.
For wide-area monitoring, a novel technique is proposed to characterize the system dynamic
response in near real-time in terms of not only damping and frequency but also
mode-shape, the latter being critical for corrective control action. Real-time simulation
in Opal-RT is carried out to illustrate the effectiveness and practical feasibility of the proposed
approach. Potential problem with wide-area closed-loop continuous control using
FACTS devices due to continuously time-varying latency is addressed through the proposed
modification of the traditional phasor POD concept introduced by ABB. Adverse
impact of limited bandwidth availability due to networked communication is established
and a solution using an observer at the PMU location has been demonstrated.
Impact of wind penetration on the system dynamic performance has been analyzed along
with effectiveness of damping control through proper coordination of wind farms and
HVDC links. For multi-terminal HVDC (MTDC) grids the critical issue of autonomous
power sharing among the converter stations following a contingency (e.g. converter outage)
is addressed. Use of a power-voltage droop in the DC link voltage control loops
using remote voltage feedback is shown to yield proper distribution of power mismatch
according to the converter ratings while use of local voltages turns out to be unsatisfactory.
A novel scheme for adapting the droop coefficients to share the burden according
to the available headroom of each converter station is also studied.
The effectiveness of the proposed approaches is illustrated through detailed frequency
domain analysis and extensive time-domain simulation results on different test systems