Abstract

The ability to accurately monitor the health of power distribution plant is a very attractive prospect for utility companies. This capability would provide a system that engineers could use to assess the real-time state of the network. Analysis of the data produced could allow for more informed decisions to be made in the areas of asset replacement and maintenance scheduling amongst others. It is widely accepted that partial discharge activity is linked with the electrical ageing/degradation of high voltage equipment. Work at Southampton is focused on obtaining a better understanding of the characteristics and trends of partial discharge events associated with medium voltage cables under, 'real life' conditions. An experiment has been developed that allows for service conditions to be applied to defective paper insulated lead covered cable samples. The samples under investigation were exposed to mechanical damage designed to replicate typical problems found on an active circuit. Partial discharge measurement was undertaken during the stressing process