Study of resonances in 1 x 25 kV AC traction systems with external balancing equipment

Abstract

© 20xx IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works.AC traction systems are 1 × 25 or 2 × 25 kV/50 Hz single-phase, nonlinear, time-varying loads that can cause power-quality problems, such as unbalanced or distorted voltages. To reduce unbalance, external balancing equipment is usually connected to these systems, forming the Steinmetz circuit. Parallel resonances can occur in these types of circuits, exciting the harmonic emissions (below 2 kHz) of railway-adjustable speed drives. This paper studies these resonances at pantograph terminals and provides analytical expressions to determine their harmonic frequencies. The expressions are validated from several traction systems in the literature and PSCAD simulations.Postprint (author's final draft