Experimental study of vertical ground-source heat pump performance evaluation for cold climate in Turkey

Abstract

Heat pump systems are recognized to be outstanding heating, cooling and water heating systems. They provide high levels of comfort as well as offering significant reductions in electrical energy use. In addition, they have very low levels of maintenance requirements and are environmentally attractive. The purpose of this study is to evaluate the experimentally performance and energy analysis of vertical ground-source heat pump (GSHP) for winter climatic condition of Erzurum, Turkey. For this aim, an experimental analysis was performed on GSHP system made up in the Energy Laboratory in the campus of Ataturk University. The experimental apparatus consisted of a ground heat exchanger, the depth of which was 53 m, a liquid-to-liquid vapor compression heat pump, water circulating pumps and other measurement and control equipments. Tests were performed under laboratory conditions for space heating, in which experimental results were obtained during January-May within the heating season of 2007. The experimentally obtained results were used to calculate the heat pump coefficient of performance (COP) and the system performance (COPs). The COP and COPs were found to be in the range of 2.43-3.55 and 2.07-3.04, respectively. This study also shows that the system proposed could be used for residential heating in the province of Erzurum which is one of the coldest climate region of Turkey.Ground-source heat pump COP Energy analyses Cold climate region