<div style="left: 165.333px; top: 267.237px; font-size: 13.3333px; font-family: serif; transform: scaleX(1.05922);" data-canvas-width="770.0533333333339">本文针对一起66kV避雷器由于质量原因导致XX变电站66kVC相避雷器爆炸的事故,通过系统监控显示、电气试验、解体检查等手</div><div style="left: 85.0393px; top: 287.237px; font-size: 13.3333px; font-family: serif; transform: scaleX(1.03813);" data-canvas-width="850.2266666666662">段重点分析了无间隙金属氧化物避雷器爆炸的原因,提出了加强避雷器结构设计选型、加强避雷器工艺管控和加强设备巡检、增加带电检测的次</div><div style="left: 85.0393px; top: 307.237px; font-size: 13.3333px; font-family: serif; transform: scaleX(1.02564);" data-canvas-width="546.6666666666666">数,定期进行红外测温,逐步开展机器人智能巡检等改进措施,以提高避雷器的运行可靠性。</div></jats:p