'Institute of Electrical and Electronics Engineers (IEEE)'
Doi
Abstract
The influence of selected control strategies on the level
of low-order current harmonic distortion generated by an inverter
connected to a distorted grid is investigated through a combination
of theoretical and experimental studies. A detailed theoretical
analysis, based on the concept of harmonic impedance, establishes
the suitability of inductor current feedback versus output
current feedback with respect to inverter power quality. Experimental
results, obtained from a purpose-built 500-W, three-level,
half-bridge inverter with an L-C-L output filter, verify the efficacy of inductor current as the feedback variable, yielding an
output current total harmonic distortion (THD) some 29% lower
than that achieved using output current feedback. A feed-forward
grid voltage disturbance rejection scheme is proposed as a means to
further reduce the level of low-order current harmonic distortion.
Results obtained from an inverter with inductor current feedback
and optimized feed-forward disturbance rejection show a THD of
just 3% at full-load, representing an improvement of some 53% on
the same inverter with output current feedback and no feed-forward
compensation. Significant improvements in THD were also
achieved across the entire load range. It is concluded that the use
of inductor current feedback and feed-forward voltage disturbance
rejection represent cost–effect mechanisms for achieving improved
output current quality