We consider joint control of a switchable capacitor and a D-STATCOM for
voltage regulation in a distribution circuit with intermittent load. The
control problem is formulated as a two-timescale optimal power flow problem
with chance constraints, which minimizes power loss while limiting the
probability of voltage violations due to fast changes in load. The control
problem forms the basis of an optimization problem which determines the sizes
of the control devices by minimizing sum of the expected power loss cost and
the capital cost. We develop computationally efficient heuristics to solve the
optimal sizing problem and implement real-time control. Numerical experiments
on a circuit with high-performance computing (HPC) load show that the proposed
sizing and control schemes significantly improve the reliability of voltage
regulation on the expense of only a moderate increase in cost.Comment: 10 pages, 7 figures, submitted to HICSS'1