This paper presents a fuzzy inference system for voltage/reactive power
control in distribution substations. The purpose is go forward to automation
distribution and its implementation in isolated power systems where control
capabilities are limited and it is common using the same applications as in
continental power systems. This means that lot of functionalities do not apply
and computational burden generates high response times. A fuzzy controller,
with logic guidelines embedded based upon heuristic rules resulting from
operators at dispatch control center past experience, has been designed.
Working as an on-line tool, it has been tested under real conditions and it has
managed the operation during a whole day in a distribution substation. Within
the limits of control capabilities of the system, the controller maintained
successfully an acceptable voltage profile, power factor values over 0,98 and
it has ostensibly improved the performance given by an optimal power flow based
automation system