The Horizontal Test Stand (HTS) SRF Cavity and Cryomodule 1 (CM1) of eight
9-cell, 1.3GHz SRF cavities are operating at Fermilab. For the cryogenic
control system, how to hold liquid level constant in the cryostat by regulation
of its Joule-Thompson JT-valve is very important after cryostat cool down to
2.0 K. The 72-cell cryostat liquid level response generally takes a long time
delay after regulating its JT-valve; therefore, typical PID control loop should
result in some cryostat parameter oscillations. This paper presents a type of
PID parameter self-optimal and Time-Delay control method used to reduce
cryogenic system parameters' oscillation.Comment: 7 pp. Cryogenic Engineering Conference and International Cryogenic
Materials Conference CEC-ICMC 2011, 13-17 June 2011. Spokane, Washingto