Analisis Gangguan Pada Sistem Gardu Listrik Berbasis Gas Insulated Switchgear 150 kV Dengan Metode High Voltage Test

Abstract

The insulator system in substations is essential in maintaining safety and efficiency in electricity transmission and distribution lines. The purpose of this research is to conduct High Voltage tests to check possible malfunctions in a gas-insulated switchgear (GIS) in a 150 kV substation following IEC standard 62271-203. Insulation Resistance (IR) measurement results for components in the GIS system show that the system still has high insulation resistance for the R, S, and T phases. High voltage testing results for the three-phase Gas Insulated Switchgear also did not exhibit current leakage, meaning the system still operates satisfactorily.  Insulator pada gardu induk memegang peranan penting dalam menjaga keamanan dan efisiensi dalam sistem transmisi dan distribusi listrik. Tujuan dari penelitian ini adalah melakukan pengujian dengan menggunakan metode pegujian tegangan tinggi (High Voltage Test) untuk memeriksa kemungkinan kerusakan pada gardu induk 150 kV yang dilengkapi dengan Gas Insulated Switchgear (GIS) sesuai dengan standar IEC 62271-203. Hasil pengukuran Insulation Resistance (IR) untuk komponen pada sistem GIS menunjukan bahwa sistem tersebut masih memiliki tahanan isolasi yang tinggi untuk fase R, S dan T. Hasil pengujian untuk Gas Insulated Switchgear ketika dialiri listrik tegangan tinggi untuk tiga fase (R, S dan T) juga tidak menunjukan adanya arus bocor sehingga dapat dipastikan bahwa sistem tersebut masih berjalan dengan baik