Increasing DG Capacity of Existing Networks through Reactive Power Control and Curtailment

Abstract

Renewable energy sources (RES), especially wind turbines, have become more important during the last years. An increasing number of distributed generation (DG) units are connected to weak medium voltage distribution networks in rural areas where they have a large influence on the voltage and the line losses. Voltage rise is in this case often a limiting factor for the maximum amount of DG capacity. Already current wind turbines with a capacity of 2 MW can often not easily be connected to existing 10 kV feeders. To increase the DG capacity of existing networks without reinforcement DG units can be controlled. This paper proposes abandoning unity power factor used today and letting the converters used as network interface of many new wind turbine generators absorb reactive power to reduce the voltage level. Since reactive power has great influence on losses in the network the use of reactive power is limited. Line losses due to the transfer of reactive power are taken into account in this study. Furthermore the use of curtailment is analysed. Simulations of voltage change and line losses when using reactive power control by the connected wind turbines and curtailment in a simple test system are presented. Without reinforcement of the network it was possible to increase the DG capacity from 2;7MW to more than 4MW in the test network without violating voltage limits. Line losses increase but to a reasonable extent and lost energy due to curtailment is insignificant