Adaptive Protection and Control in Power System for Wide-Area Blackout Prevention

Abstract

This paper presents a new approach in adaptive outof-step (OOS) protection settings in power system in real-time. The proposed method uses extended equal area criterion (EEAC) to determine the critical clearing time (CCT) and critical clearing angle (CCA) of the system, which are vital information for OOS protection setting calculation. The dynamic model parameters and the coherency groups of the system for EEAC analysis are determined in real time to ensure that the newly calculated settings suit with the prevalent system operating condition. The effectiveness of the method is demonstrated in a simulated data from 16-machine 68-bus system model

    Similar works