4 research outputs found

    Investigation of flow in data rack

    No full text
    The main purpose of this paper was to set up a functioning numerical model of data rack verified by an experimental measurement. The verification of the numerical model was carried out by means of the PIV method (Particle Image Velocimetry). The numerical model was "found" while using the assumed and preset values from the experimental measurement which represent boundary conditions. The server model was conceived as a four-channel with a controlled flow rate without simulation of heat transfer. The flow rate in each channel was implemented by means of pressure loss. The numerical model was further used for simulation of several phases and configurations of data rack (21U rack space) fitted with two server workstations Dell Precision R5400. The flow field in the inlet of data rack in the front of the workstations were observed and evaluated in such a way that a 2U-dimensional free space between the workstations was being left and the remaining inlet space was blanked-off/fully opened. The results of this paper will serve for designing optimization treatment of data rack from the viewpoint of cooling efficiency both within the data rack and within the data center design

    Flow field mapping in data rack model

    No full text
    The main objective of this study was to map the flow field inside the data rack model, fitted with three 1U server models. The server model is based on the common four-processor 1U server. The main dimensions of the data rack model geometry are taken fully from the real geometry. Only the model was simplified with respect to the greatest possibility in the experimental measurements. The flow field mapping was carried out both experimentally and numerically. PIV (Particle Image Velocimetry) method was used for the experimental flow field mapping, when the flow field has been mapped for defined regions within the 2D/3D data rack model. Ansys CFX and OpenFOAM software were used for the numerical solution. Boundary conditions for numerical model were based on data obtained from experimental measurement of velocity profile at the output of the server mockup. This velocity profile was used as the input boundary condition in the calculation. In order to achieve greater consistency of the numerical model with experimental data, the numerical model was modified with regard to the results of experimental measurements. Results from the experimental and numerical measurements were compared and the areas of disparateness were identified. In further steps the obtained proven numerical model will be utilized for the real geometry of data racks and data

    Flow in data racks

    No full text
    This paper deals with the flow in data racks. The aim of this work is to find a new arrangement of elements regulating the flow in the data rack so that the aerodynamic losses and the recirculation zones were minimized. The main reason for solving this problem is to reduce the costs of data racks cooling. Another problem to be solved is a reverse flow in the servers, thus not cooled, occuring due to the underpressure in the recirculation zones. In order to solve the problem, the experimental and numerical model of 27U data rack fitted with 10 pieces of server models with a total input of 10 kW was created. Different configurations of layout of elements affecting the flow in the inlet area of the data rack were compared. Depending on the results achieved, design solutions for the improvement of existing solutions were adopted and verified by numerical simulations

    Flow in data racks

    No full text
    This paper deals with the flow in data racks. The aim of this work is to find a new arrangement of elements regulating the flow in the data rack so that the aerodynamic losses and the recirculation zones were minimized. The main reason for solving this problem is to reduce the costs of data racks cooling. Another problem to be solved is a reverse flow in the servers, thus not cooled, occuring due to the underpressure in the recirculation zones. In order to solve the problem, the experimental and numerical model of 27U data rack fitted with 10 pieces of server models with a total input of 10 kW was created. Different configurations of layout of elements affecting the flow in the inlet area of the data rack were compared. Depending on the results achieved, design solutions for the improvement of existing solutions were adopted and verified by numerical simulations