1 research outputs found

    High frequency short-circuit inductance for model transformer

    No full text
    Currently, the International Electrotechnical Commission (IEC) standard (IEC62271-100) requires that the transformer limited fault (TLF) interruption shall be verified in the test duty T10, the amplitude factor of which is defined as 1.7 for the transient recovery voltage (TRV). But, the TRV measurements for the TLF at various transformers show that the factor is mostly lower than 1.7. The reason for the low values is considered to be that the short-circuit inductance of transformer at the TRV frequency region is lower than that at the power frequency, and consequently the factor is lower than the standard value 1.7. But, the frequency-dependence of the short-circuit inductance of transformer has not been clarified yet. We measured the short-circuit inductances of model transformer with and without the iron core. The short-circuit inductance with the iron core becomes small and equals to one without the iron core at the TRV frequency region. We concluded that this is the reason for the phenomena of low amplitude factor. In addition, we showed that the frequency-dependence of short-circuit inductance could be explained by taking eddy current within an iron core and copper windings into consideration
    corecore