Less is More: Real-time Failure Localization in Power Systems
Cascading failures in power systems exhibit non-local propagation patterns
which make the analysis and mitigation of failures difficult. In this work, we
propose a distributed control framework inspired by the recently proposed
concepts of unified controller and network tree-partition that offers strong
guarantees in both the mitigation and localization of cascading failures in
power systems. In this framework, the transmission network is partitioned into
several control areas which are connected in a tree structure, and the unified
controller is adopted by generators or controllable loads for fast timescale
disturbance response. After an initial failure, the proposed strategy always
prevents successive failures from happening, and regulates the system to the
desired steady state where the impact of initial failures are localized as much
as possible. For extreme failures that cannot be localized, the proposed
framework has a configurable design, that progressively involves and
coordinates more control areas for failure mitigation and, as a last resort,
imposes minimal load shedding. We compare the proposed control framework with
Automatic Generation Control (AGC) on the IEEE 118-bus test system. Simulation
results show that our novel framework greatly improves the system robustness in
terms of the N-1 security standard, and localizes the impact of initial
failures in majority of the load profiles that are examined. Moreover, the
proposed framework incurs significantly less load loss, if any, compared to
AGC, in all of our case studies
Failure Localization in Power Systems via Tree Partitions
Cascading failures in power systems propagate non-locally, making the control
and mitigation of outages extremely hard. In this work, we use the emerging
concept of the tree partition of transmission networks to provide an analytical
characterization of line failure localizability in transmission systems. Our
results rigorously establish the well perceived intuition in power community
that failures cannot cross bridges, and reveal a finer-grained concept that
encodes more precise information on failure propagations within tree-partition
regions. Specifically, when a non-bridge line is tripped, the impact of this
failure only propagates within well-defined components, which we refer to as
cells, of the tree partition defined by the bridges. In contrast, when a bridge
line is tripped, the impact of this failure propagates globally across the
network, affecting the power flow on all remaining transmission lines. This
characterization suggests that it is possible to improve the system robustness
by temporarily switching off certain transmission lines, so as to create more,
smaller components in the tree partition; thus spatially localizing line
failures and making the grid less vulnerable to large-scale outages. We
illustrate this approach using the IEEE 118-bus test system and demonstrate
that switching off a negligible portion of transmission lines allows the impact
of line failures to be significantly more localized without substantial changes
in line congestion
Dynamically protected cat-qubits: a new paradigm for universal quantum computation
We present a new hardware-efficient paradigm for universal quantum
computation which is based on encoding, protecting and manipulating quantum
information in a quantum harmonic oscillator. This proposal exploits
multi-photon driven dissipative processes to encode quantum information in
logical bases composed of Schr\"odinger cat states. More precisely, we consider
two schemes. In a first scheme, a two-photon driven dissipative process is used
to stabilize a logical qubit basis of two-component Schr\"odinger cat states.
While such a scheme ensures a protection of the logical qubit against the
photon dephasing errors, the prominent error channel of single-photon loss
induces bit-flip type errors that cannot be corrected. Therefore, we consider a
second scheme based on a four-photon driven dissipative process which leads to
the choice of four-component Schr\"odinger cat states as the logical qubit.
Such a logical qubit can be protected against single-photon loss by continuous
photon number parity measurements. Next, applying some specific Hamiltonians,
we provide a set of universal quantum gates on the encoded qubits of each of
the two schemes. In particular, we illustrate how these operations can be
rendered fault-tolerant with respect to various decoherence channels of
participating quantum systems. Finally, we also propose experimental schemes
based on quantum superconducting circuits and inspired by methods used in
Josephson parametric amplification, which should allow to achieve these driven
dissipative processes along with the Hamiltonians ensuring the universal
operations in an efficient manner.Comment: 28 pages, 11 figure
Failure Localization in Power Systems via Tree Partitions
Cascading failures in power systems propagate non-locally, making the control and mitigation of outages extremely hard. In this work, we use the emerging concept of the tree partition of transmission networks to provide an analytical characterization of line failure localizability in transmission systems. Our results rigorously establish the well perceived intuition in power community that failures cannot cross bridges, and reveal a finer-grained concept that encodes more precise information on failure propagations within tree-partition regions. Specifically, when a non-bridge line is tripped, the impact of this failure only propagates within well-defined components, which we refer to as cells, of the tree partition defined by the bridges. In contrast, when a bridge line is tripped, the impact of this failure propagates globally across the network, affecting the power flow on all remaining transmission lines. This characterization suggests that it is possible to improve the system robustness by temporarily switching off certain transmission lines, so as to create more, smaller components in the tree partition; thus spatially localizing line failures and making the grid less vulnerable to large-scale outages. We illustrate this approach using the IEEE 118-bus test system and demonstrate that switching off a negligible portion of transmission lines allows the impact of line failures to be significantly more localized without substantial changes in line congestion
Line Failure Localization of Power Networks. Part I: Non-cut outages
Transmission line failures in power systems propagate non-locally, making the control of the resulting outages extremely difficult. In this work, we establish a mathematical theory that characterizes the patterns of line failure propagation and localization in terms of network graph structure. It provides a novel perspective on distribution factors that precisely captures Kirchhoff's Law in terms of topological structures. Our results show that the distribution of specific collections of subtrees of the transmission network plays a critical role on the patterns of power redistribution, and motivates the block decomposition of the transmission network as a structure to understand long-distance propagation of disturbances. In Part I of this paper, we present the case when the post-contingency network remains connected after an initial set of lines are disconnected simultaneously. In Part II, we present the case when an outage separates the network into multiple islands
- …