15 research outputs found

    Fuzzy Set Approach to Transformer Differential Relay

    No full text
    In the process of decision making by a transformer differential relay often occurs a measure of uncertainty. It is so, because the differential current may be caused by other reasons than internal faults. Because of that, to improve reliability the relays are comparatively slow, because the correct decision requires at least one full cycle of current, and sometimes the delay is much longer. To improve it one may use several criteria and apply the so called `a fuzzy set approach'. Fuzzy sets have become a very powerful mathematical tool to describe quantitatively uncertain values and relations between them. They are perfect to solve the decision making problems in cases when symptoms are uncertain and the situation unclear. If applied to the protective relays they make the best compromise between the speed and selectivity of the protection

    A multi-criteria differential transformer relay based on fuzzy logic

    No full text
    This paper presents a digital relay scheme for the primary protection of power transformers. A multi-criteria algorithm is developed based on fuzzy sets for the decision making part of the scheme. The cost of wrong decision-making and the amount of information inflow are used along with several standard criteria to improve the reliability of the protection. It is shown that the proposed scheme, if properly tuned, can enhance the sensitivity and selectivity of the digital relay and mitigate problems associated with conventional relay schemes

    Simplifying and improving protection of temporary and unusual bus configurations with microprocessor-based relays

    No full text
    Breaker substitution, stub bus, and station bypass are temporary substation configurations used to facilitate the maintenance of primary equipment while keeping assets in service and supplying loads. These configurations provide considerable operational advantages but create challenges for protection systems. Traditional solutions to temporary bus configurations required for electromechanical relays utilize test and bypass switches to ensure the affected relays are provided with the appropriate currents and voltages and the trip signals are routed to the appropriate breakers. In some cases, spare relays, settings changes, and the rerouting of pilot signals and communications have been required. All these manual operations increase the danger of misoperation when making changes, during temporary configurations, or when restoring to the normal configuration. As a result, temporary bus configurations have been carefully considered and often avoided, resulting in underutilization of the network assets. This paper shows how modern microprocessor-based relays can simplify applications under temporary bus configurations, eliminate the need for any manual reconfiguration, and improve the performance of protection. These benefits stem from the ability to connect multiple current and voltage inputs, the ability to trip multiple breakers, communication between relays, and programmable logic, allowing automatic detection and dynamic response to temporary bus configurations

    Generator split-phase protection

    No full text
    The stator winding of a hydrogenerator is often made up of coils with multiple turns in the same slot. It is therefore possible for faults to develop between adjacent turns on the same phase (turn-toturn faults). These faults cannot be detected by the stator differential protection because there is no difference between the neutral- and terminal-side currents. Split-phase protection, an overcurrent element responding to the difference between the currents in the winding parallel branches, is typically provided to detect these faults. Ideally, the split-phase element should be sensitive enough to detect a single shorted turn. Despite the fact that the current in this turn can be six to seven times the machine nominal current, the current seen by the split-phase protection can be quite small, in the order of one-twentieth of the generator full-load current. In addition, a spurious split-phase current can be measured due to current transformer (CT) errors, saturation during external faults in particular. Therefore, primary considerations in the application of split-phase protection are the method of measuring the difference in the currents between the parallel branches and the proper selection of the CT used for this purpose

    Tutorial on operating characteristics of microprocessor-based multiterminal line current differential relays

    No full text
    Line current differential (87L) protection schemes face extra challenges compared with other forms of differential protection, in addition to the traditional requirements of sensitivity, speed, and immunity to current transformer saturation. Some of these challenges include data communication, alignment, and security; line charging current; and limited communications bandwidth. To address these challenges, microprocessor-based 87L relays apply elaborate operating characteristics, which are often different than a traditional percentage differential characteristic used for bus or transformer protection. These sophisticated elements may include adaptive restraining terms, apply an Alpha Plane, use external fault detection logic for extra security, and so on. While these operating characteristics provide for better performance, they create the following challenges for users: x Understanding how the 87L elements make the trip decision. x Understanding the impact of 87L settings on sensitivity and security, as well as grasping the relationship between the traditional percentage differential characteristic and the various 87L operating characteristics. x Having the ability to transfer settings between different 87L operating characteristics while keeping a similar balance between security and dependability. x Testing the 87L operating characteristics. These issues become particularly significant in applications involving more than two currents in the line protection zone (multiterminal lines) and lines terminated on dual-breaker buses. This paper is a tutorial on this relatively new protection topic and offers answers to the outlined challenges

    Controlling Autoreclosing on Overhead Lines with Underground Cable Sections Using Traveling-Wave Fault Location Based on Measurements from Line Terminals Only

    No full text
    The paper explains principles of fault locating based on traveling waves measured only at line terminals for hybrid lines comprising overhead and cable sections. The paper introduces an adaptive autoreclosing control logic to allow or cancel reclosing based on the location of the fault. The paper includes examples that explain and illustrate these principles
    corecore