    Aktive Laermminderung durch Gegenschall Abschlussbericht

    No full text
    In the context of a pilot project, 'ANC ventilation sound absorbers', a conventional sound absorber was successfully replaced by an active silencer, which resulted in a more than 80% by volume reduction of the passive absorption material required. The pressure loss is in the same range as with the conventional system, i.e. about 25 Pa. Widening of the cross-section, as in the conventional system, is not required. The electronic control system consumes about 30 W in the compensation state, i. e. it is not significant.Im Rahmen des Pilotprojektes 'ANC-Lueftungsschalldaempfer' konnte im Zuluftstrang einer Lueftungsanlage an der FH Bingen eine konventioneller Kulissenschalldaempfer durch einen Aktiv-Schalldaempfer erfolgreich substituiert werden. Gegenueber dem substituierten Kulissenschalldaempfer konnte das passive Absorptionsmaterial im ANC-Lueftungsschalldaempfer um ueber 80 Vol% reduziert werden. Der verursachte Druckverlust liegt mit ca. 25 Pa in der Groessenordnung des Druckverlustes des Kulissenschalldaempfers. Dieser erreicht diesen guenstigen Druckverlust aber nur deshalb, weil der Querschnitt im Bereich des Kulissenschalldaempfers entsprechend aufgeweitet wurde, worauf beim ANC-Lueftungsschalldaempfer verzichtet werden konnte. Die elektrische Betriebsleistung der Regelelektronik im Kompensationsfall wurde mit ca. 30W ermittelt und faellt damit nicht nennenswert ins Gewicht. (orig.)SIGLEAvailable from TIB Hannover: F01B707 / FIZ - Fachinformationszzentrum Karlsruhe / TIB - Technische InformationsbibliothekDeutsche Bundesstiftung Umwelt, Osnabrueck (Germany)DEGerman