    VRF IN HEATING MODE

    Get PDF
    Variable refrigerant flow (VRF) air conditioning system has become attractive due to better energy performances than traditional air conditioning systems. However, the shortcoming of no outdoor air (OA) intake has not been solved thoroughly. A new VRF and outdoor air processing unit combined air conditioning system is proposed and simulated. The first obstacle is that there is no well-known simulation tool for VRF unit in heating mode. A VRF model of condenser-number independence is developed and validated first. The combined system is modeled by integrating the individual sub-system or component models into a complete system. The average error of the developed model to predict heating capacity, input power and COP are 7.87%, 12.45% and 6.19% respectively