This article presents the Prony method as a filtering technique for distance relays. First, the effect of non-filtered frequency components generated by Wind Power Plants in distance relays is evaluated in a simplified model of a doubly fed induction generator, resulting in an error of apparent impedance measurement. Then, the effects of non-filtered frequency components for typical distance relay are presented. The error in apparent impedance measurement is evaluated in reach and operation time of the relay; a distorted characteristic of the mho distance relay is shown in the impedance plane. Finally, Prony method as a filtering technique is implemented as a solution of the apparent impedance measurement error, and the simulated case and a real fault event are evaluated to validate the proposed distance relay algorithm. Thus the asynchronous frequency components of voltage and current signals are identified and filtered, as a result the performance of the distance relay is enhanced
Is data on this page outdated, violates copyrights or anything else? Report the problem now and we will take corresponding actions after reviewing your request.