99 research outputs found
Grid Simulator for Testing a Wind Turbine on Offshore Floating Platform
An important aspect of such offshore testing of a wind turbine floating platform is electrical loading of the wind turbine generator. An option of interconnecting the floating wind turbine with the onshore grid via submarine power cable is limited by many factors such as costs and associated environmental aspects (i.e., an expensive and lengthy sea floor study is needed for cable routing, burial, etc). It appears to be a more cost effective solution to implement a standalone grid simulator on a floating platform itself for electrical loading of the test wind turbine. Such a grid simulator must create a stable fault-resilient voltage and frequency bus (a micro grid) for continuous operation of the test wind turbine. In this report, several electrical topologies for an offshore grid simulator were analyzed and modeled
Dielectric model of point charge defects in insulating paraelectric perovskites
Some point defects (i.e., oxygen vacancies) create deep trapping levels in the bandgap of the paraelectric phase ferroelectric crystals. Under applied DC field the traps release electrons via the Poole-Frenkel mechanism and become charged. The electric field of a point charge polarizes the crystal locally reducing its permittivity. In this paper a simple theory is proposed for calculating the DC field dependent apparent (measureable) permittivity of a paraelectric crystal with point charge defects. It is shown that the apparent permittivity of a paraelectric crystal may be sufficiently lower as compared with the defectless crystal. This reduction is in addition to the possible reduction of the apparent permittivity associated with the interfacial "dead" layers and strain
Bivariate Hermite Interpolation and Numerical Curves
AbstractIn this paper, Hermite interpolation by bivariate algebraic polynomials of total degree ⩽nis considered. The interpolation parameters are the values of a function and its partial derivatives up to some ordernν−1 at the nodeszν=(xν, yν),ν=1, …, s, wherenνis the multiplicity ofzν. The sequence N={n1, …, ns; n} of multiplicities associated with the degree of interpolating polynomials is investigated. Some results of the paper were announced in [GHS93]
Recommended from our members
Wind Power Plant Short Circuit Current Contribution for Different Fault and Wind Turbine Topologies: Preprint
This paper presents simulation results for SC current contribution for different types of WTGs obtained through transient and steady-state computer simulation software
Recommended from our members
Variable Frequency Operations of an Offshore Wind Power Plant with HVDC-VSC: Preprint
In this paper, a constant Volt/Hz operation applied to the Type 1 wind turbine generator. Various control aspects of Type 1 generators at the plant level and at the turbine level will be investigated. Based on DOE study, wind power generation may reach 330 GW by 2030 at the level of penetration of 20% of the total energy production. From this amount of wind power, 54 GW of wind power will be generated at offshore wind power plants. The deployment of offshore wind power plants requires power transmission from the plant to the load center inland. Since this power transmission requires submarine cable, there is a need to use High-Voltage Direct Current (HVDC) transmission. Otherwise, if the power is transmitted via alternating current, the reactive power generated by the cable capacitance may cause an excessive over voltage in the middle of the transmission distance which requires unnecessary oversized cable voltage breakdown capability. The use of HVDC is usually required for transmission distance longer than 50 kilometers of submarine cables to be economical. The use of HVDC brings another advantage; it is capable of operating at variable frequency. The inland substation will be operated to 60 Hz synched with the grid, the offshore substation can be operated at variable frequency, thus allowing the wind power plant to be operated at constant Volt/Hz. In this paper, a constant Volt/Hz operation applied to the Type 1 wind turbine generator. Various control aspects of Type 1 generators at the plant level and at the turbine level will be investigated
Recommended from our members
Development and Testing of Commercial Prototype Wind-Electric Battery Charging Station
The technical aspects of charging 12-volt (V) batteries with a small permanent magnet wind-turbine generator suggested that a special battery-charging station be developed. Scientists at the National Renewable Energy Laboratory (NREL) conducted research on several possible configurations of wind-electric battery-charging stations. Based on preliminary modeling and test results, the optimal system for this application was the one with individual charge controllers. This paper presents the development efforts and test results of a commercial prototype wind-electric battery-charging station designed and manufactured by Ascension Technology, a Division of Applied Power Corporation (APC). The system, which is powered by a 3-kilowatt (kW) wind turbine, was tested at the National Wind Technology Center (NWTC). The paper discusses control strategies to improve system performance, and includes recommendations for system integrators based on the testing experience accumulated at the NWTC
Recommended from our members
Symmetrical and Unsymmetrical Fault Currents of a Wind Power Plant: Preprint
This paper investigates the short-circuit behavior of a wind power plant for different types of wind turbines. Both symmetrical faults and unsymmetrical faults are investigated. The size of wind power plants (WPPs) keeps getting bigger and bigger. The number of wind plants in the U.S. has increased very rapidly in the past 10 years. It is projected that in the U.S., the total wind power generation will reach 330 GW by 2030. As the importance of WPPs increases, planning engi-neers must perform impact studies used to evaluate short-circuit current (SCC) contribution of the plant into the transmission network under different fault conditions. This information is needed to size the circuit breakers, to establish the proper sys-tem protection, and to choose the transient suppressor in the circuits within the WPP. This task can be challenging to protec-tion engineers due to the topology differences between different types of wind turbine generators (WTGs) and the conventional generating units. This paper investigates the short-circuit behavior of a WPP for different types of wind turbines. Both symmetrical faults and unsymmetrical faults are investigated. Three different soft-ware packages are utilized to develop this paper. Time domain simulations and steady-state calculations are used to perform the analysis
PSCAD Modules Representing PV Generator
Photovoltaic power plants (PVPs) have been growing in size, and the installation time is very short. With the cost of photovoltaic (PV) panels dropping in recent years, it can be predicted that in the next 10 years the contribution of PVPs to the total number of renewable energy power plants will grow significantly. In this project, the National Renewable Energy Laboratory (NREL) developed a dynamic modeling of the modules to be used as building blocks to develop simulation models of single PV arrays, expanded to include Maximum Power Point Tracker (MPPT), expanded to include PV inverter, or expanded to cover an entire PVP. The focus of the investigation and complexity of the simulation determines the components that must be included in the simulation. The development of the PV inverter was covered in detail, including the control diagrams. Both the current-regulated voltage source inverter and the current-regulated current source inverter were developed in PSCAD. Various operations of the PV inverters were simulated under normal and abnormal conditions. Symmetrical and unsymmetrical faults were simulated, presented, and discussed. Both the three-phase analysis and the symmetrical component analysis were included to clarify the understanding of unsymmetrical faults. The dynamic model validation was based on the testing data provided by SCE. Testing was conducted at SCE with the focus on the grid interface behavior of the PV inverter under different faults and disturbances. The dynamic model validation covers both the symmetrical and unsymmetrical faults
Wind Power Opportunities in St. Thomas, USVI: A Site-Specific Evaluation and Analysis
This NREL technical report utilizes a development framework originated by NREL and known by the acronym SROPTTC to assist the U.S. Virgin Islands in identifying and understanding concrete opportunities for wind power development in the territory. The report covers each of the seven components of the SROPTTC framework: Site, Resource, Off-take, Permitting, Technology, Team, and Capital as they apply to wind power in the USVI and specifically to a site in Bovoni, St. Thomas. The report concludes that Bovoni peninsula is a strong candidate for utility-scale wind generation in the territory. It represents a reasonable compromise in terms of wind resource, distance from residences, and developable terrain. Hurricane risk and variable terrain on the peninsula and on potential equipment transport routes add technical and logistical challenges but do not appear to represent insurmountable barriers. In addition, integration of wind power into the St. Thomas power system will present operational challenges, but based on experience in other islanded power systems, there are reasonable solutions for addressing these challenges
- …