2,082 research outputs found

    A filter design approach to maximize ampacity of cables in nonsinusoidal power systems

    Get PDF
    This paper presents an optimal design of the C-type passive filters for the effective utilization of the power cables under nonsinusoidal conditions based on maximization of the harmonic derating factor (HDF) of a power cable, where maintaining the load true power factor at an acceptable range is desired. According to IEEE Standard 519, the total harmonic distortions of the voltage and current measured at the point of common coupling are taken into account as main constraints of the proposed approach. The presented numerical results show that the proposed approach provides higher current carrying capacity, or ampacity of the cables under nonsinusoidal conditions when compared to the traditional approaches based on minimization of the current total harmonic distortion and maximization of the true load power factor. A numerical case study is presented to demonstrate the proposed approach

    Optimal design of single-tuned passive filters using response surface methodology

    Get PDF
    This paper presents an approach based on Response Surface Methodology (RSM) to find the optimal parameters of the single-tuned passive filters for harmonic mitigation. The main advantages of RSM can be underlined as easy implementation and effective computation. Using RSM, the single-tuned harmonic filter is designed to minimize voltage total harmonic distortion (THDV) and current total harmonic distortion (THDI). Power factor (PF) is also incorporated in the design procedure as a constraint. To show the validity of the proposed approach, RSM and Classical Direct Search (Grid Search) methods are evaluated for a typical industrial power system

    Comparison of different optimization criteria for optimal sizing of hybrid active power filters parameters

    Get PDF
    Praise Worthy Prize granted a permission for Brunel University London to archive this article in BURA.Harmonic distortion in power systems has increased considerably due to the increasing use of nonlinear loads in industrial firms and elsewhere. This distortion can give rise to overheating in all sectors of the power system, leading to reduced efficiency, reliability, operational life and sometimes failure. This article seeks to propose a new methodology for the optimal sizing of hybrid active power filter (HPF) parameters in order to overcome the difficulties in hybrid power filters design when estimating the preliminary feasible values of the parameters. Sequential Quadratic Programming based on FORTRAN subroutines is used to find out the planned filter size in two different optimization criteria depending on design concerns. The first criterion is to minimize the total voltage harmonic distortion. The second one is to maximize the load power factor, while taking into account compliance with IEEE standard 519-1992 limits for the total voltage harmonic distortion and the power factor.The effectiveness of the proposed filter is discussed using four exemplary case

    Optimal sizing of C-type passive filters under non-sinusoidal conditions

    Get PDF
    In the literature, much attention has been focused on power system harmonics. One of its important effects is degradation of the load power factor. In this article, a C-type filter is used for reducing harmonic distortion, improving system performance, and compensating reactive power in order to improve the load power factor while taking into account economic considerations. Optimal sizing of the C-type filter parameters based on maximization of the load power factor as an objective function is determined. The total installation cost of the C-type filter and that of the conventional shunt (single-tuned) passive filter are comparatively evaluated. Background voltage and load current harmonics are taken into account. Recommendations defined in IEEE standards 519-1992 and 18-2002 are taken as the main constraints in this study. The presented design is tested using four numerical cases taken from previous publications, and the proposed filter results are compared with those of other published techniques. The results validate that the performance of the C-type passive filter as a low-pass filter is acceptable, especially in the case of lower short-circuit capacity systems. The C-type filter may achieve the same power factor with a lower total installation cost than a single-tuned passive filter

    Optimal passive filter design for effective utilization of cables and transformers under non-sinusoidal conditions

    Get PDF
    Transformers and cables have overheating and reduced loading capabilities under non-sinusoidal conditions due to the fact that their losses increases with not only rms value but also frequency of the load current. In this paper, it is aimed to employ passive filters for effective utilization of the cables and transformers in the harmonically contaminated power systems. To attain this goal, an optimal passive filter design approach is provided to maximize the power factor definition, which takes into account frequency-dependent losses of the power transmission and distribution equipment, under non-sinusoidal conditions. The obtained simulation results show that the proposed approach has a considerable advantage on the reduction of the total transmission loss and the transformer loading capability under non-sinusoidal conditions when compared to the traditional optimal filter design approach, which aims to maximize classical power factor definition. On the other hand, for the simulated system cases, both approaches lead to almost the same current carrying (or loading) capability value of the cables. © 2014 IEEE.This work is supported by Turkish Republic Ministry of Science, Industry and Technology and BEST Transformers Co. under the project number of 01008.STZ.2011 - 2

    Harmonics mitigation based on the minimization of non-linearity current in a power system

    Get PDF
    Harmonic issues in power systems are becoming an important topic for industrial customers and power suppliers alike due to their adverse effects in both consumer appliances as well as for utility suppliers. Consumers should seek to reduce harmonic pollution, regardless of voltage or current distortion already present in the network. This article suggests a new method for suppressing distortions by using the non-linearity current index (NLCI) to determine the shunt single-tuned passive filter (STPF) compensator value in non-sinusoidal power systems, with the objective of maintaining the power factor within desired limits. The objective of the proposed method is to minimize the nonlinear current of customer’s loads in the power system at the point of common coupling (PCC). Moreover, the proposed design takes into consideration other practical constraints for the total voltage and individual harmonic distortion limits, ensuring compliance with (Institute of Electrical and Electronics Engineers) IEEE 519-2014 guidelines, maintaining distortions at an acceptable level while also abiding by the capacitor loading constraints established in IEEE 18-2012. The performance of the optimally designed compensator is assessed using well documented IEEE standards based on numerical examples of nonlinear loads taken from previous publications

    Approach of Passive Filters using NSGA II in industrial installations: Part I

    Full text link
    The optimization of passive filters in industrial systems has been presented by different computational methods. The objective of this paper is to develop a computational algorithm with NSGA II to select the configuration and design parameters of a set of passive filters for industrial installations. As a methodology, the optimization problem was addressed using three independent objective functions of innovative character for compensation of harmonics through passive filters as a multiobjective problem. The results were the computational solution to this problem that determines a set of Pareto optimal solutions (Frontier). In addition, the computational tool has several new features such as: calculates the parameters that characterize the filters, but also selects the type of configuration and the number of branches of the filter in each candidate bar according to a set of pre-established configurations according to PRODIST-M8 (Brazilian Standard) and IEEE 519-2014. Also determine solutions with good power quality indicators (THD, TDD and NPV) for several characteristic and non-characteristic scenarios of the system that allow to represent: daily variations of the load, and variations of system parameters and filters. It evaluates the cost of energy bills in an industrial power grid that has different operating conditions (characteristic scenarios) and evaluates the economic effect of harmonic filters as reactive power compensators