Local secondary control for inverter-based islanded microgrids with accurate active-power sharing under high load conditions
Local secondary control has been successfully used to regulate the frequency of inverterbased islanded microgrids without using communications.
In this scenario, noticeable steady-state deviations have been observed in active power sharing caused by the inherent clock drift of the digital processors that implement each inverter local control. This paper presents a control scheme that performs frequency regulation and improves the active power sharing under high load conditions, thus alleviating the impact of clock drifts in this situation. The study introduces a theoretical analysis that quantifies the steady-state deviations in active power sharing. It also includes a design procedure for the control parameters based on static and dynamic specifications.
Experimental tests validate the expected features of the proposed control. The experimental setup is based on a laboratory microgrid equipped with three independent
digital signal processors with different clock drifts.Postprint (author's final draft
Performance evaluation of secondary control policies with respect to digital communications properties in inverter-based islanded microgrids
A key challenge for inverted-based microgrids working in islanded mode is to maintain their own frequency and voltage to a certain reference values while regulating the active and reactive power among distributed generators and loads. The implementation of frequency and voltage restoration control policies often requires the use of a digital communication network for real-time data exchange (tertiary control covers the coordi- nated operation of the microgrid and the host grid). Whenever a digital network is placed within the loop, the operation of the secondary control may be affected by the inherent properties of the communication technology. This paper analyses the effect that properties like transmission intervals and message dropouts have for four existing representative approaches to secondary control in a scalable islanded microgrid. The simulated results reveals pros and cons for each approach, and identifies threats that properly avoided or handled in advance can prevent failures that otherwise would occur. Selected experimental results on a low- scale laboratory microgrid corroborate the conclusions extracted from the simulation study.Peer ReviewedPostprint (author's final draft
Secondary Frequency and Voltage Control of Islanded Microgrids via Distributed Averaging
In this work we present new distributed controllers for secondary frequency
and voltage control in islanded microgrids. Inspired by techniques from
cooperative control, the proposed controllers use localized information and
nearest-neighbor communication to collectively perform secondary control
actions. The frequency controller rapidly regulates the microgrid frequency to
its nominal value while maintaining active power sharing among the distributed
generators. Tuning of the voltage controller provides a simple and intuitive
trade-off between the conflicting goals of voltage regulation and reactive
power sharing. Our designs require no knowledge of the microgrid topology,
impedances or loads. The distributed architecture allows for flexibility and
redundancy, and eliminates the need for a central microgrid controller. We
provide a voltage stability analysis and present extensive experimental results
validating our designs, verifying robust performance under communication
failure and during plug-and-play operation.Comment: Accepted for publication in IEEE Transactions on Industrial
Electronic
Voltage Stabilization in Microgrids via Quadratic Droop Control
We consider the problem of voltage stability and reactive power balancing in
islanded small-scale electrical networks outfitted with DC/AC inverters
("microgrids"). A droop-like voltage feedback controller is proposed which is
quadratic in the local voltage magnitude, allowing for the application of
circuit-theoretic analysis techniques to the closed-loop system. The operating
points of the closed-loop microgrid are in exact correspondence with the
solutions of a reduced power flow equation, and we provide explicit solutions
and small-signal stability analyses under several static and dynamic load
models. Controller optimality is characterized as follows: we show a one-to-one
correspondence between the high-voltage equilibrium of the microgrid under
quadratic droop control, and the solution of an optimization problem which
minimizes a trade-off between reactive power dissipation and voltage
deviations. Power sharing performance of the controller is characterized as a
function of the controller gains, network topology, and parameters. Perhaps
surprisingly, proportional sharing of the total load between inverters is
achieved in the low-gain limit, independent of the circuit topology or
reactances. All results hold for arbitrary grid topologies, with arbitrary
numbers of inverters and loads. Numerical results confirm the robustness of the
controller to unmodeled dynamics.Comment: 14 pages, 8 figure
Plug-and-play and coordinated control for bus-connected AC islanded microgrids
This paper presents a distributed control architecture for voltage and
frequency stabilization in AC islanded microgrids. In the primary control
layer, each generation unit is equipped with a local controller acting on the
corresponding voltage-source converter. Following the plug-and-play design
approach previously proposed by some of the authors, whenever the
addition/removal of a distributed generation unit is required, feasibility of
the operation is automatically checked by designing local controllers through
convex optimization. The update of the voltage-control layer, when units plug
-in/-out, is therefore automatized and stability of the microgrid is always
preserved. Moreover, local control design is based only on the knowledge of
parameters of power lines and it does not require to store a global microgrid
model. In this work, we focus on bus-connected microgrid topologies and enhance
the primary plug-and-play layer with local virtual impedance loops and
secondary coordinated controllers ensuring bus voltage tracking and reactive
power sharing. In particular, the secondary control architecture is
distributed, hence mirroring the modularity of the primary control layer. We
validate primary and secondary controllers by performing experiments with
balanced, unbalanced and nonlinear loads, on a setup composed of three
bus-connected distributed generation units. Most importantly, the stability of
the microgrid after the addition/removal of distributed generation units is
assessed. Overall, the experimental results show the feasibility of the
proposed modular control design framework, where generation units can be
added/removed on the fly, thus enabling the deployment of virtual power plants
that can be resized over time
Analysis of the effect of clock drifts on frequency regulation and power sharing in inverter-based islanded microgrids
© 2018 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes,creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works.Local hardware clocks in physically distributed computation devices hardly ever agree because clocks drift apart and the drift can be different for each device. This paper analyses the effect that local clock drifts have in the parallel operation of voltage source inverters (VSIs) in islanded microgrids (MG). The state-of-the-art control policies for frequency regulation and active power sharing in VSIs-based MGs are reviewed and selected prototype policies are then re-formulated in terms of clock drifts. Next, steady-state properties for these policies are analyzed. For each of the policies, analytical expressions are developed to provide an exact quantification of the impact that drifts have on frequency and active power equilibrium points. In addition, a closed-loop model that accommodates all the policies is derived, and the stability of the equilibrium points is characterized in terms of the clock drifts. Finally, the implementation of the analyzed policies in a laboratory MG provides experimental results that confirm the theoretical analysis.Peer ReviewedPostprint (author's final draft
- …