1,639 research outputs found
Recommended from our members
Integrating Smart Ceiling Fans and Communicating Thermostats to Provide Energy-Efficient Comfort
The project goal was to identify and test the integration of smart ceiling fans and communicating thermostats. These highly efficient ceiling fans use as much power as an LED light bulb and have onboard temperature and occupancy sensors for automatic operationbased on space conditions. The Center for the Environment (CBE) at UC Berkeley led the research team including TRC, Association for Energy Affordability (AEA), and Big Ass Fans (BAF). The research team conducted laboratory tests, installed99 ceiling fans and 12 thermostats in four affordable multifamily housing sites in California’s Central Valley, interviewed stakeholders to develop a case study, developed an online design tool and design guide, outlined codes and standards outreach, and published several papers.The project team raised indoor cooling temperature setpoints and used ceiling fans as the first stage of cooling; this sequencing of ceiling fans and air conditioningreducesenergy consumption, especially during peak periods, while providing thermal comfort.The field demonstration resulted in 39% measured compressor energy savings during the April–October cooling seasoncompared to baseline conditions, normalized for floor area. Weather-normalized energy use varied from a 36% increase to 71% savings, withmedian savings of 15%.This variability reflects the diversity in buildings, mechanical systems, prior operation settings, space types, andoccupants’ schedules,preferences, and motivations. All commercial spaces with regular occupancy schedules (and twoof the irregularly-occupied commercial spaces and one of the homes) showed energy savings on an absolute basis before normalizing for warmer intervention temperatures,and 10 of 13 sites showed energy savings on a weather-normalized basis. The ceiling fans provided cooling for one site for months during hot weather when the coolingequipment failed.Occupants reported high satisfaction with the ceiling fans and improved thermal comfort. This technology can apply to new and retrofit residential and commercial buildings
Development of Economic Water Usage Sensor and Cyber-Physical Systems Co-Simulation Platform for Home Energy Saving
In this thesis, two Cyber-Physical Systems (CPS) approaches were considered to reduce residential building energy consumption. First, a flow sensor was developed for residential gas and electric storage water heaters. The sensor utilizes unique temperature changes of tank inlet and outlet pipes upon water draw to provide occupant hot water usage. Post processing of measured pipe temperature data was able to detect water draw events. Conservation of energy was applied to heater pipes to determine relative internal water flow rate based on transient temperature measurements. Correlations between calculated flow and actual flow were significant at a 95% confidence level. Using this methodology, a CPS water heater controller can activate existing residential storage water heaters according to occupant hot water demand. The second CPS approach integrated an open-source building simulation tool, EnergyPlus, into a CPS simulation platform developed by the National Institute of Standards and Technology (NIST). The NIST platform utilizes the High Level Architecture (HLA) co-simulation protocol for logical timing control and data communication. By modifying existing EnergyPlus co-simulation capabilities, NIST’s open-source platform was able to execute an uninterrupted simulation between a residential house in EnergyPlus and an externally connected thermostat controller. The developed EnergyPlus wrapper for HLA co-simulation can allow active replacement of traditional real-time data collection for building CPS development. As such, occupant sensors and simple home CPS product can allow greater residential participation in energy saving practices, saving up to 33% on home energy consumption nationally
Agent-based control for decentralised demand side management in the smart grid
Central to the vision of the smart grid is the deployment of smart meters that will allow autonomous software agents, representing the consumers, to optimise their use of devices and heating in the smart home while interacting with the grid. However, without some form of coordination, the population of agents may end up with overly-homogeneous optimised consumption patterns that may generate significant peaks in demand in the grid. These peaks, in turn, reduce the efficiency of the overall system, increase carbon emissions, and may even, in the worst case, cause blackouts. Hence, in this paper, we introduce a novel model of a Decentralised Demand Side Management (DDSM) mechanism that allows agents, by adapting the deferment of their loads based on grid prices, to coordinate in a decentralised manner. Specifically, using average UK consumption profiles for 26M homes, we demonstrate that, through an emergent coordination of the agents, the peak demand of domestic consumers in the grid can be reduced by up to 17% and carbon emissions by up to 6%. We also show that our DDSM mechanism is robust to the increasing electrification of heating in UK homes (i.e. it exhibits a similar efficiency)
Recommended from our members
Technical Review of Residential Programmable Communicating Thermostat Implementation for Title 24-2008
Policy Design for Controlling Set-Point Temperature of ACs in Shared Spaces of Buildings
Air conditioning systems are responsible for the major percentage of energy
consumption in buildings. Shared spaces constitute considerable office space
area, in which most office employees perform their meetings and daily tasks,
and therefore the ACs in these areas have significant impact on the energy
usage of the entire office building. The cost of this energy consumption,
however, is not paid by the shared space users, and the AC's temperature
set-point is not determined based on the users' preferences. This latter factor
is compounded by the fact that different people may have different choices of
temperature set-points and sensitivities to change of temperature. Therefore,
it is a challenging task to design an office policy to decide on a particular
set-point based on such a diverse preference set. As a result, users are not
aware of the energy consumption in shared spaces, which may potentially
increase the energy wastage and related cost of office buildings. In this
context, this paper proposes an energy policy for an office shared space by
exploiting an established temperature control mechanism. In particular, we
choose meeting rooms in an office building as the test case and design a policy
according to which each user of the room can give a preference on the
temperature set-point and is paid for felt discomfort if the set-point is not
fixed according to the given preference. On the other hand, users who enjoy the
thermal comfort compensate the other users of the room. Thus, the policy
enables the users to be cognizant and responsible for the payment on the energy
consumption of the office space they are sharing, and at the same time ensures
that the users are satisfied either via thermal comfort or through incentives.
The policy is also shown to be beneficial for building management. Through
experiment based case studies, we show the effectiveness of the proposed
policy.Comment: Journal paper accepted in Energy & Buildings (Elsevier
- …