Extension of a Virtual Refrigerant Charge Sensor

By Woohyun Kim and James E. Braun

Abstract

The primary goal of the work described in this paper was to evaluate and extend a virtual refrigerant charge sensor (VRC) for determining refrigerant charge for equipment having variable-speed compressors and fans. To evaluate the accuracy of the VRC, data were first collected from previous laboratory tests for different systems and over a wide range of operating conditions. In addition, new laboratory tests were performed to consider conditions not available within the existing data set. The systems for the new laboratory tests were two residential ductless split heat pump systems that employ a variable-speed compressor and R-410a as the refrigerant. Based on the evaluations, the original virtual charge sensor (termed Model I) was found to work well in estimating the refrigerant charge for systems with a variable-speed compressor under many operating conditions. However, for extreme test conditions such as low outdoor temperatures and low compressor speed, the VRC needed to be improved. To overcome the limitations, the model associated with the VRC sensor was modified to include a term involving the inlet quality to the evaporator (termed model II). Both the model I and II showed good performance in terms of predicting charge levels for systems with a constant speed compressor, but model II gave better performance for systems with a variable-speed compressor. However, when the superheat of the compressor was zero, neither model I nor II could accurately predict charge level. Therefore, a third approach (Model III) was developed that includes the discharge superheat of the compressor. This model improved performance for a laboratory-tested system that included a number of points with no superheat entering the compressor

Topics: Virtual Sensor, Refrigerant Charge, Variable speed compressor, Fault detection, Fault diagnosis
Publisher: Purdue University
Year: 2012
OAI identifier: oai:docs.lib.purdue.edu:iracc-2242
Provided by: Purdue E-Pubs

Suggested articles

Preview

Citations

  1. (2005). An experimental study on the performance of inverter heat pump with a variation of frequency and refrigerant charging rate,
  2. (2002). Charge Inventory System Modeling and Validation for Unitary Air Conditioners, Ph.D. Thesis, Herrick Labs
  3. (2003). Commercial Buildings Energy Consumption Suvrvey 2003., U.S Survey
  4. (1996). Common faults and their impacts for rooftop air conditioner,
  5. (2002). Effect of refrigerant charge on the performance of air conditioning systems,
  6. (1964). Estimation of steady-state steam void-fraction by means of the principle of minimum entropy production.
  7. Evaluation and Demonstration of a Virtual Refrigerant Charge Sensor,
  8. (2007). Evaluation of a Virtual Refrigerant Charge Level Gauge for Vapor Compression Equipment,” IIR Congress of Refrigeration,
  9. (2010). Evaluation of a Virtual Refrigerant Charge sensor, Compressor, Refrigeration and Air Conditioning Conferences,
  10. (1990). Modeling the Effects of Refrigerant Charging on Air Conditioner Performance Characteristics for Three Expansion Devices, Ph.D,
  11. (2003). Performance investigation of a variable-speed vapor compression system for fault detection and diagnosis,
  12. (2001). The effect of improper refrigerant charge on the performance of a heat pump with an electronic expansion valve and capillary tube,
  13. (1987). The Effect of Void Fraction Correlation and Heat Flux Assumption on Refrigerant Charge Inventory Predictions,

To submit an update or takedown request for this paper, please submit an Update/Correction/Removal Request.